102 RemotEye II User Manual 50024-014
UPS Shutdown Events
RemotEye II can initiate output shutdown upon the occurrence of six different UPS events, Input Power
Failure, Low Battery, UPS Overload, UPS Over Temperature, Recurring Schedule and Non-recurring
Schedule. Users can view the current setting of these events on UPS Shutdown Events page in UPS
Management menu. To alter these settings, log in as an administrator, and configure the UPS shutdown
events action and delay times accordingly. Click the Set Value button when finish. (See Pg. 54 for
details)
Scenario:
Shutdown Event: AC Failed
Status: Client Shutdown
Delay (Min): 7 (default)
Warning Interval (sec): 30 (default)
UPS Output Shutdown Delay (Sec) 180(default)
UPS Events - AC failed 22:20:00
22 : 20 : 00 22 : 27 : 00 22 : 30 : 00
Client’s local shutdown delay (Sec):120(default)
22 : 20 : 00 22 : 27 : 00 22 : 29 : 00
INVERTER
OUTPUT
SHUTDOWN
CLIENT ON
CLIENT OFF