RemotEye II User Manual 50024-014 103
Managing the UPS Recurring & Non-recurring Schedule
RemotEye II supports two output shutdown schedule (1) Recurring Schedule; (2) Non-recurring
Schedule.
Note: Before managing the UPS Shutdown Schedule, please make sure that the Date and Time
configured in RemotEye II is correct.
Scenario
Shutdown Event: Recurring Schedule
Status: UPS Output shutdown
Delay (Min): 10(default)
Warning Interval (sec): 60(default)
UPS Shutdown Delay (Sec): 180(default)
Shutdown & Restart day & time: Monday 22:20:00 ----- 99:99:99
Shutdown & Restart day & time: Tuesday 99:99:99 ----- 09:00:00
Note: 99:99:99 indicates the RemotEye II will ignore the Restart Time on Monday, and the Shutdown time
on Tuesday.
Monday Tuesday
22 : 20 : 00 22 : 30 : 00 22 : 33 : 00 09:00:00
INVERTER
OUTPUT
SHUTDOWN