RemotEye II User Manual 50024-014 79
UPS Alarm List
ID
Object
Alarm Occur Message
Alarm Removal Message
1
…/upsAlarmBatteryBad
Battery test has detected battery
failure. Contact Toshiba
authorized service center for
replacement.
Battery failure condition, detected
by previous battery test, has been
removed.
2
…/upsAlarmOnBattery
The UPS is on batteries; it is
supplying output power from its
batteries.
The UPS is no longer on batteries;
output power is not being supplied
from its batteries.
3
…/upsAlarmLowBattery
Low battery. Continued operation
on batteries will deplete them
entirely & result in UPS Output
shutdown.
The UPS is no longer reporting a
state of Low Batteries.
4
…/upsAlarmDepletedBattery
UPS has depleted batteries &
unable to support critical loads.
Turn off excess equipment to
reduce load.
The batteries are no longer
depleted; they have been charged
to a supportive level.
5
…/upsAlarmTempBad
The UPS is overheating. Check
for UPS fan failure or high
ambient temperature ( > 40°C /
104°F)
The UPS is no longer overheating.
6
…/upsAlarmInputBad
The input voltage is out of
tolerance. UPS may switch to
Battery Mode to support the load.
The input voltage is back within
tolerance.
7
…/upsAlarmOutputBad
The output voltage is out of
tolerance. Check the output
voltage.
N/A
8
…/upsAlarmOutputOverload
UPS is overloaded. UPS will
switch to bypass or shutdown.
Turn off excess equipment to
reduce load.
The UPS is no longer being
overloaded.
9
…/upsAlarmOnBypass
The UPS is in Stop (Bypass)
mode.
The UPS is no longer in Stop
(Bypass) mode.
10
…/upsAlarmBypassBad
A bypass condition is out of
tolerance. Check the input and
output voltage.
N/A
11
…/upsAlarmOutputOffAsReq
uested
The UPS output has shutdown as
requested.
N/A
12
…/upsAlarmUpsOffAsReques
ted
The UPS system has shutdown
as requested.
N/A
13
…/upsAlarmChargerFailed
An uncorrected problem has
been detected within the UPS
charger subsystem.
N/A
14
…/upsAlarmUpsOutputOff