80 RemotEye II User Manual 50024-014
15
…/upsAlarmUpsSystemOff
The UPS system is off.
N/A
16
…/upsAlarmFanFailure
Fan failure! UPS system possibly
overheating. Contact Toshiba
authorized service center
immediately.
Fans are no longer failing.
17
…/upsAlarmFuseFailure
The failure of one or more fuses
has been detected. Contact your
Toshiba authorized service
center.
N/A
18
…/upsAlarmGeneralFault
A UPS fault condition exists.
Contact your Toshiba authorized
service center immediately.
The UPS fault condition has been
removed. Good work.
19
…/upsAlarmDiagnosticTestFa
iled
The result of the last diagnostic
test indicates a failure.
N/A
20
…/upsAlarmCommunicationL
ost
Communication lost between the
RemotEye II and the UPS.
Communication has been restored
between the RemotEye II and the
UPS.
21
…/upsAlarmAwaitingPower
N/A
N/A
22
…/upsAlarmShutdownPendin
g
A UPS output shutdown
command has been issued;
Output will turn off after delay.
OK
23
…/upsAlarmShutdownImmine
nt
The UPS output will be shutdown
in less than 30 seconds due to
previously issued shutdown
command.
N/A
24
…/upsAlarmTestInProgress
A UPS battery test is in progress.
Battery test completed.
25
…/upsAlarmPhaseRotation
Input phase rotation is incorrect.
Check input wiring for clockwise
rotation.
Input phase rotation has been
corrected.
26
…/upsAlarmReplaceBattSoon
Batteries nearing end of expected
lifetime. Contact Toshiba
authorized service center for
replacement.
Battery lifetime monitor has been
reset.
27
…/upsAlarmAsyncOperation
Inverter can not sync to input.
UPS cannot switch from Run to
Stop until input frequency
stabilizes.
N/A
28
…/upsAlarmInputOverCurrent
UPS reporting Input Overcurrent.
Contact Toshiba authorized
service center for examination of
fault.
The cause of the Input
Overcurrent condition has been
removed. The UPS is no longer in
a INOC fault mode.