Appendix 5 (cont.) Soft Starter Settings Record
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F024
Pump Flex Decel Mode
Pump Flex Control /
Deceleration Ramp
0 = Disabled (coast to stop)
1 = Enabled, except after OL trip
2 = Enabled, continued Decel even
if there is an OL trip
1
0
Disabled
F025
Begin Decel Level (BDL),
Immediate Drop Down Torque
0 - 100 % of Output Voltage 1% 60%
F026 Decel Shut Off Voltage 0 to (BDL minus 1)% Voltage 1% 30%
F027 Decel Ramp Time 1 – 60 Seconds 1 second
10
seconds
F028
Restart
Restart Delay Time
(Sequential Start Delay)
0 = Disabled, or
1-999 seconds after a Power Loss
(Status can be read in F054)
1 second
0
Disabled
F029
Reserved for Factory Use