TE2 Series Digital Solid State Soft Starter User Manual 89 | Page
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F085
Fault History and Run Data
Fault History #1, Latest
Fault
0 = No fault history, or
Fault # 1 - 57: see Fault code list
N/A
Read
Only
F086
Time Stamp, Fault #1
Based on F078-80
00.00 - 23.59 (hh.mm)
[hh = 00 - 23; mm = 00 - 59]
F087
Date Stamp, Fault #1
Based on F076-77
01.01 - 12.31 (MM.DD)
[MM = 01 - 12; DD = 01 - 31]
F088
Fault History #2, Previous
Fault
0 = No fault history, or
Fault # 1 - 57: see Fault code list
F089 Time Stamp, Fault #2
00.00 - 23.59 (hh.mm)
[hh = 00 - 23; mm = 00 - 59]
F090 Date Stamp, Fault #2
01.01 - 12.31 (MM.DD)
[MM = 01 - 12; DD = 01 - 31]
F091
Fault History #3, Oldest
Fault
0 = No fault history, or
Fault # 1 - 57: see Fault code list
F092 Time Stamp, Fault #3
00.00 - 23.59 (hh.mm)
[hh = 00 - 23; mm = 00 - 59]
F093 Date Stamp, Fault #3
01.01 - 12.31 (MM.DD)
[MM = 01 - 12; DD = 01 - 31]
F094 Run Time, Hours 000.0 - 999.9 hours
F095
Run Time,
1000 Hour Overflow
0000 - 9999 thousand hours
F096 Run Cycle Counter 0000 - 9999 times
F097
Run Cycle Counter
10K overflow
0000 - 9999 10 thousand times
Fn # Group Function Description Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F098
Phase and Frequency
Protection
Phase Rotation Trip
0, 1 or 2
0=Disabled, 1=ABC, 2=ACB]
1 0
F099 Phase Rotation Trip Delay 1 - 3 seconds 1 1
F100
Phase Loss Trip and Delay
during Stop
0, 1-20 Seconds [0= Disabled] 1 1
F101
Phase Loss Trip and Delay
during Running
0, 1-20 Seconds [0= Disabled] 1 1