E6581158
K-17
11
Q Table of input terminal functions 3
Function
No.
Code Function Action
54 STN Inversion of ST (coasting) ON: Coast stop (gate off)
OFF: Ready for operation
55 RESN Inversion of RES ON: Acceptance of reset command
OFF ON: Trip reset
56 F+ST Combination of forward run and standby ON: Simultaneous input from F and ST
57 R+ST Combination of reverse run and standby ON: Simultaneous input from R and ST
58 AD3 Acceleration/deceleration 3 selection ON: Acceleration/deceleration 3
OFF: Acceleration/deceleration 1 or 2
59 F+AD3 Combination of forward run and
acceleration/deceleration 3
ON: Simultaneous input from F and AD3
60 R+AD3 Combination of reverse run and
acceleration/deceleration 3
ON: Simultaneous input from R and AD3
61 OCS2 Forced switching of stall prevention level 2 ON: Enabled at the value of H
OFF: Enabled at the value of H
62 HDRY Holding of RY-RC terminal output ON: Once turned on, RY-RC are held on.
OFF: The status of RY-RC changes in real time
according to conditions.
63 HDOUT Holding of OUT-NO terminal output ON: Once turned on, OUT-NO are held on.
OFF: The status of OUT-NO changes in real time
according to conditions.
64 PRUN Cancellation (clearing) of operation command from
panel
0: Operation command canceled (cleared)
1: Operation command retained
Q Table of output terminal functions 1
Function
No.
Code Function Action
0 LL Frequency lower limit ON: The output frequency is above the NN set
value.
OFF: The output frequency is equal to or less than
the NN set value.
1 LLN Inversion of frequency lower limit Inversion of LL setting
2 UL Frequency upper limit ON: Output frequency is equal to or higher than
WN value.
OFF: Output frequency is lower than WN value.
3 ULN Inversion of frequency upper limit Inversion of UL setting
4 LOW Low-speed detection signal ON: Output frequency is equal to or higher than
H value.
OFF: Output frequency is lower than H
value.
5 LOWN Inversion of low-speed detection signal Inversion of LOW setting
6 RCH Designated frequency attainment signal
(completion of acceleration/deceleration)
ON: The output frequency is equal to or less than
the specified frequency ± frequency set with
H.
OFF: The output frequency is above the specified
frequency ± frequency set with H.
7 RCHN Inversion of designated frequency attainment
signal (inversion of completion of
acceleration/deceleration)
Inversion of RCH setting
8 RCHF Set frequency attainment signal ON: The output frequency is equal to or less than
the frequency set with H ± frequency
set with H.
OFF: The output frequency is above the frequency
set with H ± frequency set with
H.
9 RCHFN Inversion of set frequency attainment signal Inversion of RCHF setting
10 FL Failure signal (trip output) ON: When inverter is tripped
OFF: When inverter is not tripped
11 FLN Inversion of failure signal (inversion of trip output) Inversion of FL setting