E6581158
E-4
5
[Setting methods]
Key operated LED display Operation
.
Displays the operation frequency. (Perform during operation stopped.)
(When standard monitor display selection H is set to [Op-
eration frequency])
CWJ
The first basic parameter “CWJ” (history function) is displayed.
CW
Press the key to change the parameter to CW (automatic torque
boost)

Pressing the ENTER key allows the reading of parameter setting.

Press the key to change the parameter to 1 (sensorless vector
control + auto-tuning). (Programmed value at the right and the his-
tory at the left)
 CW
Press the ENTER key to save the changed parameter. CW and the
parameter are displayed alternately.
Note 1: The same characteristic can be obtained by setting the V/F control mode selection parameter RV to
(automatic torque boost control) and the auto-tuning parameter H to (auto-tuning).
See 5.12
Note 2: Setting CW to automatically programs RV to .
Note 3: The accuracy of auto-tuning can be increased by specifying the rated current of the driven motor,
using the motor rated current setting parameter H.
2) When using vector control (increasing starting torque and high-precision opera-
tions)
Set the automatic control CW to (sensorless vector control + auto-tuning)
Setting Automatic control CW to (sensorless vector control + auto-tuning) provides high starting torque
bringing out the maximum in motor characteristics from the low-speed range. This suppresses changes in
motor speed caused by fluctuations in load to provide high precision operation. This is an optimum feature for
elevators and other load transporting machinery.