[14] Functions for lift Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
 0324 Drooping output filter 0.1~200.0 rad/s (Enabled if =3 or 7) 0.1/0.1 100.0 Enabled / - - 6. 16
[15] Commercial/inverter switching function Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
 0354
Commercial power/inverter switching
output selection
0:Disabled
1:Automatic switching in the event of a trip
2:Commercial power switching frequency setting
3:Commercial power switching frequency setting +
automatic switching in the event of a trip
1/1 0 Disabled /●●6. 17
 0355
Commercial power/inverter switching
frequency
0~ Hz 0.1/0.01 *2 Enabled /●●6. 17
 0356 Inverter-side switching waiting time 0.10~10.00 sec. 0.01/0.01 *1 Enabled /●●6. 17
 0357
Commercial power-side switching waiting
time
0.40~10.00 sec. 0.01/0.01 0.62 Enabled /●●6. 17
 0358
Commercial power switching frequency
holding time
0.10~10.00 sec. 0.01/0.01 2.00 Enabled /●●6. 17
*1: Default values vary depending on the capacity. See the table of K-41. *2: Inverter with a model number ending with -WN: 60.0 -WP: 50.0
[16] PID control [1/2] Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
Default
setting
Write during
running
Vector
control
PM
control
V/f Reference
 0359 PID control switching
0:No PID control
1:Process type PID control (temp./pressure, etc.)
operation
2:Speed type PID control (potentiometer, etc.)
operation
1/1 0 Disabled /●●6. 18 *1
 0360
PID control feedback control signal
selection
0:Deviation input (no feedback input)
1:VI/II (voltage/current input)
2:RR/S4 (potentiometer/voltage input)
3:RX (voltage input)
4:Optional AI1 (differential current input)
5:Optional AI2 (voltage/current input)
6: PG feedback option
1/1 0 Disabled /●●6. 18 *1
 0361 Delay filter 0.0~25.0 1/1 0.1 Enabled /●●6. 18 *1
 0362 Proportional (P) gain 0.01~100.0 0.01/0.01 0.10 Enabled /●●6. 18 *1
 0363 Integral (I) gain 0.01~100.0 0.01/0.01 0.10 Enabled /●●6. 18 *1
 0364 PID deviation upper limit ~ Hz 0.1/0.01 *2 Enabled /●●6. 18 *1
*1: For details, refer to Instruction Manual (E6581329) specified in Section 6.36. *2: Inverter with a model number ending with -WN: 60.0 -WP: 50.0