ADVANCED SETTINGS – HEAT PUMP
HP “ON” when Furnace On: Heat Pump and Furnace can operate together when
2nd stage furnace is required. HP “OFF” when Furnace On: turns off the Heat Pump
when the furnace is On (required on some gas or oil furnaces).
35
ADVANCED SETTINGS – TIMER FEATURE
Specify the number of minutes for which Stage 1 will function until Stage 2 is acti-
vated to help raise (or cool) temperature (if the temperature set point is not reached).
This unique function avoids excess compressor wear in the case where the neces-
sary temperature set point is not met through setting of the Staging Differentials. Set
to “00” to disable.