Performance Data
Cooling
4TTR2024A1 WITH WF025A14 AT 800 CFM
O.D. I.D, TOT SENS.CAP.ATENTERINGD.B.TEMF TOTAL
D.B. W.B, CAP. 72 75 78 80
59 21.4 19.2 215" 22.4' 23.0' 2.02
88 63 83,3 161 18.5 21,0 225 2.05
67 25,2 127 15,1 17,6 19,2 2.09
59 209 189 210' 22,0" 826* 220
95 63 22.7 !59 183 20,7 22.3 0,24
67 246 12.5 14.9 17,3 18.9 228
63 210 151 175 20,0 21.2" 2,35
105 67 22.8 117 14.2 16,6 18.2 2.39
71 84,7 83 10,7 13,1 14.7 2.44
63 192 14,4 16.8 19,2 19.8' 8.46
115 67 21,0 11,0 13.4 15.9 175 2.51
71 22.8 7.6 10.0 12.4 _4,0 2.56
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYOR ADDAS INDICATED)
AIRFLOW 700 900 AIRFLOW 700 9<X)
TOTALCAP X0,98 X1,01 SENS.CAP X0,94 X1,06
4TrR2024A1 WITH TVF030A14 AT 900 CFM
O,D. I.D. TOT SENS.CAP.ATENTERINGD.E,TEMP TOTAL
D.B. W,B. CAP. 72 75 78 80 KW
59 223 20.8 22.7* 23.7' 24.3" 2.09
85 53 241 172 20,9 88,7 24,3' 2.12
67 26.1 13.4 16.1 15.8 20.7 2.16
59 21.6 20,5 22.2" 23,!* 23.7' 2.27
95 63 23.5 17.0 19.7 22.4 83.7' 2.31
67 28,4 13.1 15,8 18.6 20.4 2.35
63 216 16,2 19.9 21.7" 22.2* 2.42
105 67 23,5 12,3 15.1 17.9 19,6 2.47
71 25.4 8,4 11.1 13.9 15.7 2,51
63 19.8 15,4 18.2 20.2" 29.7" 2,53
115 67 21.6 11.6 14.3 17.1 18.9 2.58
71 23.4 7.6 10.4 13.1 15.0 2.63
CORRECTIONFACTORS-OTHERAIRFLOWS(MULTIPLYORADDASINDICATED)
AIRFLOW 775 1025 AIRFLOW 775 1025
TOTALCAP X9.98 X1.01 SENS.CAP X0.93 X1.07
41TR2024A1 WITH TVF036A14 AT 900 CFM
O,D. I.D. TOT SENS.CAP.ATENTERINGD.B.TEMP TOTAL
D.B, W,B. CAP, 72 75 78 80 KW
59 223 20.7 22,7" 23.7" 243" 9,17
85 63 24,2 17.1 19.9 22.7 24.3* 220
67 96.1 13,2 16.0 18.7 20.6 224
59 91.6 20,4 22.2" 23.1" 23.7" 2,35
95 63 23.5 16.8 19.6 22,3 23.7" 9.39
67 25.4 12.9 15.7 18.4 20.3 2.43
63 21,6 16,0 18.8 21.6 22.2" 2.50
105 57 23.9 12.1 14.9 17.7 19.5 2.54
71 25.4 8.2 10,9 13,7 15.6 8.59
63 19.8 15.3 18.9 20,1' 20,7" 2.61
115 67 21,6 11.4 14.2 16.9 18.8 2,66
71 03.4 7.4 10.2 13.0 14.8 2.71
CORRECTIONFACTORS- OTHERNRFLOWS (MULTIPLYORADDASINDICATED)
AIRFLOW 775 1025 AIRFLOW 775 1025
TOTALCAP X0,98 X1.01 SENS, CAP X0,93 X1,07
4TFFI2024A1 WITH TWE018C14 AT 700 CFM
O.D. I.D, TOT SENS.CAP.ATENTERINGD.B,TEMP TOTAL
D.R, W.B. CAP, 72 75 78 80 KW
59 19.5 16.6 18.5 19.9' 20.4" 1.90
85 63 21.3 14.2 10.1 19.0 19,3 1.93
67 23,1 11.6 13.5 15.4 !66 1.97
59 19.1 16.4 18.3 !9.6" 80.1" 208
95 63 20.9 14,1 16.0 17.9 19.1 2.12
67 22.7 11.4 13.3 15.2 16,9 2.16
63 19.3 13,4 15.3 17.2 18.4 2.24
105 67 21.1 19.7 12.6 14.5 15.9 2,28
71 22.9 8.0 99 11.8 13.1 231
83 17.8 12.7 14.6 18.8 !7,7 2.36
115 67 19.4 10.0 11.9 13.8 t5.1 2.40
71 21.1 7.3 9.2 11.1 12,4 2.44
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYORADDASINDICATED)
AIRFLOW 600 800 AIRFLOW 600 500
TOTALCAP X0.97 Xl.02 SENS.CAP X0.94 X106
4_4A1 WITH 13NE024Ct4 AT 800 CFM
O.D. I,D. TOT SENS,CAP.ATENTERINGD.B. TEMF TOTAL
D.B, W.B. CAP. 72 75 78 80 KW
59 29.2 17.6 19.7 20.9" 21.5' 1.98
85 63 22.0 150 17,1 19,2 20.8 282
67 23.9 120 14.1 18.2 17.6 8,95
59 19,7 17,4 19.5 20.8* 21.1' 2,16
95 63 21.5 14.7 16,5 18.9 80,3 220
67 23.4 11.8 13,9 18,0 17.4 2.24
63 19.9 14.0 16.1 18.2 19,6 2.32
105 87 21.7 11.1 13.2 16.3 16,7 2.36
71 23.6 8,1 10.2 12.3 13.7 2.41
63 18.3 13,3 15.4 17.5 18,8" 244
115 67 20.0 10.4 12.5 14,6 16.0 2.48
71 21,8 74 9.5 11.8 13.0 253
CORREC11ONFACTORS- OTHERAIRFLOWS(MULTIPLYORADDASINDICATED)
AIRFLOW 700 900 AIRFLOW 700 90_
TOTALCAP X0.98 Xt .0! SENS.CAP X0.95 X1.09
4TrR2024A1 WITH lWE030C14 AT 900 CFM
O.D. I.D. TOT SENS,CAP,ATENTERINGD.S.TEMP TOTAL
D,B. W.B. CAP. 72 78 78 80 KW
59 21,3 19,6 21.6" 22.5" 23.1" 206
85 53 23.1 16.4 18,9 21.4 23.1" 2.10
67 25.0 12.8 15.3 17.8 19.5 2,!4
59 20.7 19.3 21.1" 22.0* 22.8* 2,24
95 63 22.5 18.1 18.6 21.2 22.6" 2.28
67 24.4 12.5 15.1 17.6 19,3 2.32
63 29.8 15.4 17.9 20,4 21,8" 2.40
105 67 22.6 11.8 t4.3 16.8 18,5 2.44
71 24.5 82 10.7 13.2 14.9 2.49
63 19.1 14.6 17.1 19.3" 19,5' 2.51
115 67 20.8 11.1 13,6 16.1 17,9 2.56
71 22.6 7.4 10,0 12.5 14.9 2,61
CORREC11ONFACTORS- OTHERAIRFLOWS (MULTIPLYORADD ASINDICATED)
AIRFLOW 775 1025 AIRFLOW 775 1026
TOTALCAP X098 X1.01 SENS. CAP X0.94 X1,06
NOTE:ALL TABLESABOVEAREATARIRATtNG CONDITIONSRATEDWITH 25FEET OF REERIGERANTLINES
DRY CO_LCONOITION(TOTALCAPACIIY ; SENSIBLE Ct,°ACI_YI
TOTALCAPACFTYCOMP KW ANDAPp OEW PT AREVALIO ONLYFORWET COIL¸ALLTEMPERATURESFNDEGREESF