Performance Data
Cooling
4TFR2030A1 WITH _JD060R9V3+TXH041A4 AT1000 CFM
O.D. I.D. TOT SENS,CAP.AT ENTERINGD.B.TEMP TOTAL
D.B. W.B. CAP. 78 75 79 80 KW
59 27.6 24.5 275 28.6* 29.2" 2.37
35 63 29.6 20.6 236 26.5 28,5 2.39
67 31.6 16.2 19.2 22.2 24.2 2.41
59 270 242 27.1" 281" 28.7* 264
95 63 29.0 20.3 23.3 26.3 29.3 267
67 31,0 16,9 190 21.9 23.9 270
63 27.3 18.6 22,5 25.5 27,3* 3,94
105 67 29.2 152 18.2 21.8 23.2 2.97
71 81.3 10.8 13.8 !6,8 18.8 3.01
63 25.6 18.8 21.8 24,8 26,0* 3.21
115 67 27.5 14.5 17.5 20.5 22.5 3.25
71 29.4 10.1 13.1 16.1 18.1 3,29
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYORADD ASINDICATED)
AIRFLOW 375 1125 AIRFLOW 975 1!25
TOTALCAP X0.98 X1.01 SENS.CAP X0.94 X1.06
4TrR2030A1 WITH 13JD060RV3+RXC02503 AT 1000 CFM
O.D. I.D. TOT SENS.CAP.ATENTERINGD.B. TEMP TOTAL
D.B. W,B. CAP. 72 75 78 80 KW
58 254 22.1 24.6 26.1" 26,7" 2.37
85 63 27.3 18.7 21.3 23.9 25.6 2.38
67 29.3 15,0 17.5 20,1 21.8 240
59 24.4 21.6 24,2 25.2" 25.8* 2.62
95 63 26.2 18.2 20,8 23.4 25,1 9,65
67 38.2 14.5 17.6 196 21.3 2.67
83 25,0 17,7 20.2 22,8 24.5 2.94
105 67 26.8 13.9 16.5 19.1 20.8 2.97
71 28.3 10.1 12,7 18.2 18,9 3.00
63 23.8 17.1 19.7 22.3 23.9* 3.23
115 67 25,6 13.4 15.9 18.5 29,2 3.27
71 27.5 9.5 12,1 14.7 16.4 3.31
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYORADDAS INDICATED)
AIRFLOW 875 1125 AIRFLOW 875 1125
TOTALCAP X0.98 X1.01 SENS.CAP X0,95 X1,05
4"rrR2030A1 WITH l"LID060RW3+RXCO31 $3 AT 1100
O,D. I.D. TOT SENS,CAP.ATENTERINGD.B.TEMP TOTAL
D.B. W.B. CAP. 72 75 76 80 KW
59 27.5 28.3 27.8* 28.8" 29.8* 2.40
85 63 29,5 2!.1 24,3 27.5 29,5* 242
67 31.5 16.4 19.6 22.8 24.9 2.44
89 26,4 24.8 26.9" 27.9* 28,6" 2,66
88 63 28.4 20.6 23.8 27,0 28,8* 2.68
67 30.4 15.9 19.1 22,3 24.4 2.71
63 26,9 19.8 23,1 26,3 27,4* 2.98
105 67 28.9 18.3 18.5 21.7 23.8 3.01
71 30.9 10.5 18.7 17.0 19.1 3.05
63 25.5 19.3 22.5 25,6" 26.2" 3.27
115 67 27.3 14.7 17.9 21.1 23.2 3.31
71 29,3 9.9 13.1 16.3 18.5 3,36
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYORADDASINDICATED)
AIRFLOW 950 1250 AIRFLOW 950 1250
TOTALCAP XO.98 X1.01 SENS, CAP X0,94 X1.06
4TTR2030A1 WITH "PJO060R9V3+RXC03603 AT1000 CFM
O,D, I.D, TOT SENS.CAP.AT ENTERINGD.8, TEMP TOTAL
D.B. W.B. CAP. 72 75 78 30 KW
59 279 24,3 273 287' 29.4' 2.35
85 63 29,9 204 334 263 283 2.37
67 31,9 16,0 190 220 240 2.39
59 26.8 23.8 26.8' 278* 28.4* 2,62
95 63 28.7 19.9 229 25.8 27,8 2.64
67 30.7 155 185 21.5 23.9 2,67
63 272 192 222 252 27.2 2.94
105 67 292 !4.9 179 209 22.9 2.97
71 312 105 135 165 18,5 3.90
63 25.3 186 21 6 24,6 260* 324
115 67 27.6 14.3 173 202 222 3.27
7! 29.5 9.9 12.9 15.9 17.8 3.31
CORRECTIONFACTORS- OTHERAIRFLOWSIMULTIPLYOR ADDAS iNDICATED)
AIRFLOW 875 1125 AIRFLOW 975 1!25
TOTALCAP XO.98 X1.01 SENS.CAP X0.94 X1.06
4TFR2030A1 WITH TUD080RV3+TXH025A4 AT 1000 CFM
O.D. LD, TOT SENS.CAP.ATENTERINGD,D.TEMP TOTAL
D.B. W.B. CAP. 72 79 78 60 KW
59 25.6 22.7 253 264* 271' 2.3!
85 63 27.5 19,2 21 9 245 26.2 233
67 29.5 15.4 180 206 224 235
59 25.1 224 250 260* 26,6" 258
95 63 270 190 216 24.2 26.0 2,60
67 29,0 152 178 204 22.1 2.62
63 26.4 18.3 209 23.5 25.2 2.87
105 67 27.4 14.5 171 197 21.4 2.90
71 29.3 10.6 13.2 158 17.5 2.93
63 23.9 17.6 20.2 22.8 24.1" 3,14
115 67 257 338 164 19.0 20.7 318
71 37,6 9.9 126 15.1 16,9 3.22
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYORADDAS INDICATED)
AIRFLOW 375 1125 AIRFLOW 875 1125
TOTALCAP XO,98 X! 01 SENS CAP X0.95 X105
4TrR2030A1 WITH TUD0e0R9V3+TXH033A4 AT 1000 CFM
O.D. I.D. TOT SENS,CAP.ATENTERINGD.B,TEMP TOTAL
D.B. W,B. CAP. 72 75 78 80
59 27.1 24.1 27.0 280' 28.7" 2.35
85 63 29.0 20,3 93.2 26,1 280 236
67 31.1 161 19,0 21.8 238 2.39
59 26.4 23.8 265" 27.5* 28,2" 2.62
95 63 28.4 20.0 229 25,8 27.7 2.64
67 30.4 15,8 187 21.6 23.5 2.67
63 26.6 19.2 22.1 25.0 26.7' 2.91
105 67 28.6 150 17.9 20.8 22.7 2.94
71 30.6 108 13.6 18.5 18,5 2.97
63 24,9 18.5 21.4 24.2 25.3* 3.18
115 67 26.8 14,3 172 20.1 22.0 3.22
71 28,7 19,0 129 15,8 17,7 3,26
OORRECllON FACTORS-OTHERAIRFLOWS(MULTIPLYOR ADDAS INDICATED)
AIRFLOW 875 1125 AIRFLOW 875 1125
TOTALCAP XO.98 X1.02 SENS. CAP X094 X1.05
NOTE:ALLTABLESABOVEAREATARI RATINGCONDITIONSRATEDWITH 25FEET OFREFRIGERANTLINES
DRY CO_LCONDITION(TOTALGi_ACITY =SENSIBLEOF,°ACI_
TOTALCN=AC_'_(COMP KWANDAPp OEWPT AREVALIODNLY FORWETCOIL ALLTEMPERATURESINDEGREESF
22-1728-01 1201 (EN) 29