Performance Data
Cooling
41'1_A1 Wnl't TUD060Rg'V3+RXC031S3 AT1200
O.D. I.D. TOT SERS,CAP.AT ENTERINGD.B.TEMP TOTAL
D.B. W.B. CAP, 72 75 78 80 KW
59 33.0 23.5 32.6 33,7" 34.4' 2.81
85 63 35.0 23.8 27.3 30,7 33.0 2.83
67 372 13.7 22.1 25,5 27.8 2.85
59 31,6 27,9 21.3 32,5' 33,2' 3,11
95 63 33.6 23,2 2_.6 30,0 32,3 3.14
67 35.6 18.6 21.5 24,9 27.0 3.16
63 31.9 22,4 25.9 39.3 316 350
106 67 33.8 17.3 20.7 24.2 26.4 383
71 35.6 12.1 15.5 16,6 21,2 3.57
63 30.2 21.7 25.1 28.6 30.4" 386
115 67 32.0 16.6 20.0 23.4 25,7 3.90
71 33.9 11.4 14.8 16,2 20.5 3,94
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYOR ADDASINDICATED)
AIRFLOW 1050 1350 AIRFLOW 1050 1350
TOTALGAP X6.96 X1.01 SERS.CAP X0.94 X1,05
4'ITR2036A1 WITH TUD060RV3+RXC_36S3 AT 1200 Cr"M
o,g, LB. TOT SENS.CAP.ATENTERINGD.B. TEMP TOTAL
D.B. W,B. CAP. 72 76 78 80 KW
59 33.7 29.0 32.6 34.4" 35.2" 2.79
85 63 35,8 242 27.7 31.2 33.6 2.81
67 37,9 13.9 22.4 26,0 23,3 284
59 3_,4 26.4 31.9 33.3" 34,0* 310
95 03 34.3 23.6 27.1 30.6 32.9 3.13
67 36,4 16.3 21.8 25.3 37.7 3.!5
63 32.5 22.6 26.3 29.6 32.2 3.49
105 67 34.5 17,5 21.0 24.6 26,9 3.52
71 36.8 12.2 15.7 19.2 21.5 3.85
63 30.7 22.0 25.5 29.0 30.9* 3.85
115 67 32.6 16.8 20.3 23.8 26.1 3.89
71 34.5 11,4 14.9 13.5 20,8 3.92
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYOR ADDASINDICATED)
AIRFLOW 1050 1350 AIRFLOW 1050 1350
TOTALCAP X0.g8 XI.01 SEN$. CAP X0,94 X1.06
4TTR_I '_TH TU_V3_-TXt'_33A4 AT1200 CFM
OJ). I,D. TOT SERE. CAP.ATEN_RING D.B,TEMP TOTAL
D,B. W,B. CAP. 72 T$ 78 90 KW
59 32.4 26.6 31.9 3,3.3* 34.0" 2.B0
85 63 34.4 23.9 27.3 30.6 32.9 2.82
67 36,5 16.8 22.1 25.5 27.8 2.84
59 31.7 28.3 3t.6 32.7" 33,4" 3.12
95 83 33.7 23.6 26.9 303 32.6 3.14
67 35.8 18,5 21.9 252 27.5 3.17
63 31.6 22.6 26,0 29,4 31,6" 3,4_
105 67 33.6 17.5 20.9 24.3 26.6 3,50
71 353 12.4 15.6 19.2 2_.4 3,53
83 29.5 21,7 25.1 26.5 29,9' 3,78
115 67 31.4 16.6 20.0 23.4 26.7 3.82
71 33.4 11.5 14.9 18.3 20.5 3.86
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYORADDAS INDICATED)
AIRFLOW 1050 1350 AIRFLOW 1050 1350
TOTALCAP X0.98 X1,01 SENS.CAP X0,95 X1.05
4"1"_36A1 WffH TUD080RV3÷TXH041 A4 AT 1200 CFM
O.D, I.D. TOT $ENS.CAP.AT ENTERINGD.B, TEMp TOTAL
D.B. W.B. CAP. 72 75 78 80 KW
59 33.3 29.2 32.7 34.2' 34.9' 2.81
85 63 35.3 24.4 279 314 33.7 2.83
67 37.4 19.1 22,6 26,1 28.5 2.85
59 32.7 28.9 324 33.6" 34.3* 3.13
95 63 34.7 24,1 276 311 33.4 3,16
67 36.8 18.8 224 25,9 28,2 3.19
63 327 23.2 267 302 32.5 3.49
105 67 34.7 18.0 21.5 25.0 27.3 3.52
71 35,6 12.7 162 19.7 22.0 3.55
63 30,7 22,3 25.8 29,3 30.9" 3.83
115 67 32,6 17.1 20.6 24.1 26,5 3,86
71 34.6 11,8 15.3 18.8 21.2 3,90
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYOR ADDASINDICATED)
AIRFLOW 1050 1350 AIRFLOW 1050 1350
TOTALCAP XQ.93 X1.01 SENS.CAP X6.94 X105
4TTR2036A1 WITH TU[_0RV3+RXC031 S3 AT 1200 CFM
O.D. I.D. TOT $ENS. CAP.ATENTERINGD.B. TEMP TOTAL
D,B. W.B. CAP. 72 76 73 80 KW
59 33.2 23.7 32,1 339* 34.6' 2,81
85 63 35.3 24,0 27.4 30.9 33.2 2.83
67 37,4 13.8 22.3 25,7 28.0 2.85
59 31.8 23.0 31,5 32,7" 33,4* 312
95 63 33.7 23,3 26.6 30.2 32,5 314
67 35.8 19.2 21.6 25,6 27,2 317
63 32,0 22.6 26.0 29,5 31,7 3.51
105 67 34.0 17.4 20,9 34.3 26,6 3,54
71 36.0 12.2 15.6 19.1 21,4 3.57
63 30,4 21.8 25,3 28.7 30,5" 3,87
115 67 32.2 16.7 20.1 23.6 25.9 3.91
71 34,1 11.5 149 18.4 20.6 3.95
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYORADDAS INDICATED)
AIRFLOW t 050 1350 AIRFLOW 1050 1350
TOTALCAP X0.98 X1.01 SENS.CAP X0.94 X1.05
4TTR2036A1 WWH TUD_0RgV_A4_L_ AT1200 CFM
O.D. I.O, TOT SENS.CAP.ATENTERINGD.B.TEMP TOTAL
D.B, W.B, CAP. 72 75 78 80 KW
59 33,7 39.0 32.6 34,4" 35,2" 2.81
85 63 35.8 24.2 27.7 31.2 33.6 2,83
67 37.9 18.9 22.4 26.0 26,3 2.85
59 32,4 28.4 31.9 33,3' 34.0* 3.12
95 63 34,3 23.6 27,1 30.6 32,9 3.14
67 36,4 16.3 21.8 25.3 27,7 3,17
63 32.5 22.8 26.3 39.8 322 3.50
105 67 34.5 17.5 21.0 24.5 26.9 3.53
71 36.5 12.2 167 192 21.5 3,57
63 30.7 22.0 285 29.0 30.9' 3.87
115 67 32,6 16,7 20,3 23,8 26,1 3,90
71 34.5 11.4 14.9 18.4 20.8 3.94
CORRECTIONF/_3"TORS- OTHER AIRFLOY#$(MULTIPLYOR ADDAS INDICATED)
AIRFLOW 1050 1350 AIRFLOW 1050 1350
TOTALCAP X098 X1.01 SENS.CAP X0,94 X1.06
NOTE:ALLTABLESABOVEAREATAPl RAll NGCONDITIONSRATEDWf]H 25 FEET OF REFRIGERANTLINES
• DRY COfL CONDITION(TOTALCAPACITY- SENSIBLECAPAC/TY)
TOTALC,_PACITY.COMP. KWAND APP SEW PT ARFVALIDONLY FORWET COIL NJ. TEMPERATUR£SIN DEGREESF
42 22-1726-O1-1201 (EN)