Performance Data
Cooling
4"i'TR2048A1 Wlllt TUD140R9V5+RXC065S3 AT 1600 CFM
O,D, 1.0. TOT SENS.CAP.ATENTERINGD.B.TEMP TOTAL
D.B. W.B. CAP. 72 75 78 80 KW
99 43.1 374 42.1 44.4* 45.4' 3.77
85 63 46.2 313 35.9 40.6 43.7 3,81
67 49.5 24.5 29,2 33.8 36.9 3,85
59 41.5 367 41,3 43.0" 43.9* 4,22
95 63 44.4 30.5 35.2 39.8 42.9 427
67 47.5 23.8 28.4 33.0 36.1 4.32
63 42.5 29.7 34.4 39.0 42.1 4.74
105 67 45.4 22.9 27,6 322 35,3 4.80
71 48,4 15.0 20.7 25.3 28,4 4.86
83 40.6 28.9 33.5 38.2 40,8" 5.21
115 67 43,4 22.1 26.8 31,4 34.5 528
71 462 t5.2 19.8 24.5 27.6 536
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYOR ADD AS INDICATED)
AIRFLOW 1400 1500 AIRFLOW 1400 1800
TOTALCAP X0.98 XI.Ol SENS,CAP X0,94 Xl.0B
4TrR2048A1 WITH "RIY100R9V4+TXH041 A4 AT 1400 CFM
O,D. I.D. TOT SENS. CAP.ATENTERINGD.B. TEMP TOTAL
D.B. W.S. CAP. 72 75 78 80 KW
59 42.8 357 39.7 43.1" 44.1" 393
86 63 45.9 304 34.4 38.4 41,1 3,97
67 49.1 24.5 28.5 32.5 35.8 401
09 41.6 35,1 39.1 42.2" 43.2' 4,39
95 63 44.7 29.8 33.9 37.9 40.6 4.44
57 47.9 24.0 28.0 32.0 34.7 4.49
63 422 28.7 32.7 36,7 39.4 4.89
1(_ 67 45.3 22,9 26.9 30.9 33.6 495
71 48.4 16,9 20.9 24.9 27.6 5.02
63 39.7 27,6 31.6 35.6 38,3 5.33
115 67 42.7 21.8 25.8 29.8 32.5 542
71 45.7 15.8 19,8 23.8 26.5 5.50
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYORADDAS INDICATED)
AIRFLOW 1225 1575 AIRFLOW 1225 1575
TOTALCAP X0.98 X1.02 SENS.CAP X0.95 X1.05
4TI_2048A1 WITH TUY100RgV4+TXH054A4 AT 1400 CFM
O.D, LD. TOT SENS. CAP.ATENTERINGD.B.TEMP TOTAL
D.B. W.S. CAP. 72 75 78 80
59 43.7 36.7 41.O 44.3* 45,4" 3.97
85 63 46.8 31.0 35.3 39,8 42,5 4.01
67 50.0 24.7 29,0 33,3 36.2 4.05
59 42.6 36.2 40.5 43.4" 44.4' 4,44
95 63 45.7 30.5 34.8 39.1 42.0 4,49
67 48.9 24.2 08.5 32.8 35.7 4.54
63 43.2 29.4 33.7 38.0 40,9 493
105 67 46.3 23.1 27.5 31.8 34.6 4.99
71 49.4 16.8 21.1 25.4 28.2 5.05
63 40.8 28.3 32.6 36,9 39.8 5,37
115 67 43,7 22,1 26.4 30.7 33.6 5.44
71 46.7 15,7 20.0 24.3 27.2 552
CORRE_ FACTORS- OTHERAIRFLOWS(MULTIPLYORADDAS INDICATED)
AIRFLOW 1225 1575 AIRFLOW 17.25 1575
TOTALCAP X0.98 X1.02 SENS.CAP X0.94 X1.06
41TR2048A1 WITH TUY100R9V4+RXC037S3 AT1400 CFM
O.D. LD. TOT SENS. CAP.ATENTERINGD.B.TEMP TOTAL
D.B. W,B. CAP, 72 75 78 80 KW
59 43,4 35,8 399 43.6' 44,6' 3.91
85 63 46.5 30.4 34.5 385 41,2 3.94
57 49,8 24.5 285 32.6 35,3 3.98
59 41.7 35.0 390 422" 43.2" 437
95 63 44.7 29.6 336 37.7 40,4 4.42
67 47.8 23,6 27,7 31,8 34.5 4.47
63 42,6 286 327 36,8 39.5 4.90
105 67 45,6 22,7 26.8 39.5 33.5 4.97
71 48,7 16,7 20.7 24,8 27.5 5.03
63 40.5 277 318 35,8 38,5 5,39
115 67 43.4 21.5 258 299 32,6 5.47
71 46.4 15.7 198 239 26.6 5.55
CORRECTIONFACTORS-OTHERNRFLOWS (MULTIFLYOR ADDAS INDICATED)
AIRFLOW 1225 1575 AIRFLOW 1225 1575
TOTALCAP X0.98 X1.02 SENS,CAP X0.95 X1,05
4TrR2048A1 WITH THY100RgV4+RXC054S3 AT1400 CFM
O.D. I,D. TOT SENS, CAP,ATENTERINGD.B,TEMP TOTAL
D.B. W,B, CAP. 72 75 78 80 KW
59 43.4 354 39.5 43.5* 44.5" 3.91
55 63 46.5 39.1 34.1 38.2 40.9 3.94
67 49.8 241 28.2 32.2 350 3,95
59 41.7 34.5 35.7 42.0* 431" 4.37
95 63 447 29,3 333 374 40,1 4.42
97 47.8 23,3 27,4 31A 34,1 4.47
63 42.6 28.3 324 36.4 39.1 4.91
195 57 45.6 22,4 26.5 30.5 33.2 4.97
71 48.7 16,4 20.4 24.5 27,2 5,04
63 40,5 27.4 31.5 355 38.2 5,39
115 67 43.4 215 25.5 29,6 323 5,47
71 46,4 15.5 19,5 23.6 26.3 5.56
CORRECTIONFACTORS- OTHERAIRFLOWS(MULTIPLYOR ADDAS iNDICATED)
AIRFLOW 1225 1575 AIRFLOW 1225 1575
TOTALCAP X0.98 X1.02 SENS.CAP X0.95 X1,05
4TrR2048A1 WITH TUY100RgV4+RXH063S3 AT 1400 CFM
O.D. I.D, TOT SENS. CAP.ATENTERINGD,B.TEMP TOTAL
D,B. W.B. CAP, 72 75 78 80 KW
59 45.0 37.2 41.5 45.3" 46.4" 3.90
85 63 482 31.4 357 40,1 42.9 3.94
67 51.5 25.0 294 33.7 36.5 3.98
59 43.2 36,3 40.6 43.8' 44.8* 4.37
95 63 46.2 30.5 34.9 39.2 42.1 4.42
67 49,4 24,2 28.5 32,9 35.8 4.47
63 44.0 29.6 33.9 38.2 41.1 4.90
105 67 47.1 23.2 27,6 31.9 34.8 4.97
7! 50,2 16.8 21,2 25.5 28.4 5,04
63 41.8 28.6 33.0 37.3 40.2 5.38
115 67 44.8 22.3 26.6 31.0 33.9 5.47
71 47.8 15.9 20.2 24.6 27.5 5.56
CORRECTIONFACTORS-OTHERAIRFLOWS(MULTIPLYOR ADDASINDICATED)
AIRFLOW 1225 1575 AIRFLOW 1225 1575
TOTALCAP X0.98 X102 SENS.CAP X0.94 Xl ,C_
NOTE:ALLTABti:S ABOVEAREATARI RATINGCOND_NS RATEDWITH 25 FEETOF REFRIGERANTLINES
' DRYCOIL CONDITION(TOTALCAPACITY- SENSIBLECARACI'W)
TOTAL CAPAC_, COMP KWANDAPP OEW PT ARE VALIDONLY FOR WET COIL ALLTEMPERATDRE9IN DEGREES F