51CG-SVX06D-E4
Table 20 - Correction factors to apply when glycol is used in water loops
Fluid Type
Glycol Concentration %
Evaporator Condenser
Performance
F-CC F-PI
Evaporator
F-FLEVP F-PDEVP
Condenser
F-FLCDS F-PDCDS
Water only 0 0 1.00 1.00 1.00 1.00 1.00 1.00
Ethylene Glycol
10 0 0.99 1.00 1.02 1.02 1.00 1.00
20 0 0.98 1.00 1.05 1.06 1.00 1.00
30 0 0.97 1.00 1.10 1.10 1.00 1.00
0 10 1.00 1.00 1.00 1.00 1.02 1.05
0 20 1.00 1.01 1.00 1.00 1.04 1.09
0 30 1.00 1.02 1.00 1.00 1.08 1.14
Mono-Propylene Glycol
10 0 0.99 1.00 1.01 1.05 1.00 1.01
20 0 0.97 1.00 1.03 1.10 1.00 1.00
30 0 0.96 1.00 1.05 1.17 1.00 1.01
0 10 1.00 1.01 1.00 1.00 1.01 1.06
0 20 1.00 1.01 1.00 1.00 1.02 1.13
0 30 0.99 1.02 1.00 1.00 1.05 1.21