42
Programming
PKG-SVP01B-EN
(On units with Traq dampers only)
For Outside Air Preheat Ctrl, Use Sensor
Connected To: VCM MODULE AUX TEMP INPUT
Possible Values: VCM Module Aux Temp Input
WSM Mixed Air Temp Input
1. Pressing the NEXT key will display the following screen.
Monitor Specific Temp Input, Use Sensor
Connected To: RTM ZONE TEMP INPUT
Factory Presets: RTM Zone Temp Input
Possible Values: RTM Zone Temp Input
NSB Zone Sensor
RTM Aux Temp Input
Heat Module Aux Temp Input
ECEM Return Air Temp Input
No Sensor Selected
1. Pressing the NEXT key will display the following screen.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
Outside Air Ventilation Setup
(On units with a VCM or airside economizer)
Outside Air Ventilation Setup Submenu
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
(On units with an airside economizer and IGV or VFD)
OA Flow Compensation Function: DISABLED
Use Fixed OA Damper Minimum Position
Possible Values: Enabled, Disabled
Enabled 2nd line = OA Damper Min Pos Depends on IGV/VFD Pos
Disabled 2nd line = Use Fixed OA Damper Minimum Position
1. Pressing the NEXT key will display the following screen.
SETUP