22
SS-SVN016A-EN
Pairing 1 or 2
Figure 8. Pairing 1 or 2 for Symbio Condenser to Electromechanical Air Handler
Symbio Condenser
Electromechanical Air Handler Constant Volume
THERMOSTAT OR
ZONE SENSOR WIRE
OR
SensorSensor
UC-J15-2
LTB2-G
LTB2-B1
LTB2-R
LTB2-B2
CONTROL WIRE
AB-J18-1
UC-J21-3
T-StatT-Stat
ADAPTER BOARD
IMC -
J15
1 2 3 4
COMMON
24VAC OUT
IMC +
1 2 3
MODBUS -
MODBUS +
COMMON
J16
J18
INDOOR FAN RUN OUT
COMMON
1 2
INDOOR FAN HI SPD OUT
COMMON
1 2
J17
(AB) ONLY FIELD
CONNECTIONS SHOWN
LTB2
UC-J15-2
B2
R
B1
Y2
Y1
G
J
W2
W1
AB-J15-1
SYMBIO 700
(UC) ONLY FIELD
CONNECTIONS SHOWN
24VAC OUT
LIMIT/SHED
1 2
24VAC OUT
LIMIT/SHED
1 2
J16
T-STAT W1/O
T-STAT G/VAV CHANGE
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
1 2 3 4 5 6 7 8 9
T-STAT GND
J21
T-STAT W1/O
T-STAT G/VAV CHANGE
T-STAT W2
T-STAT Y2
T-STAT X2
T-STAT PULLDOWN-T
1 2 3 4 5 6 7 8 9
T-STAT GND
J21
R (24VAC OUT)
T-STAT Y1
LTB2-W1
LTB2-Y2
UC-J21-6
Zone Sensor or Thermostat Connections
See “Thermostat and Zone Sensor Wiring,” p. 9 for details on how to wire a zone sensor to a
Symbio condenser.
NNootteess::
• Symbio 700 thermostat connection J21-1 (R) is current limited. Alternately, wire the
thermostat R-wire to Adapter Board J15-1 and thermostat C-wire to Symbio adapter
board J15-2.
• If a zone sensor is installed, air handler electric heat will not operate.
CCoonnddeennsseerr aanndd AAiirr HHaannddlleerr PPaaiirr WWiirriinngg IInnffoorrmmaattiioonn