26
SS-SVN016A-EN
• Baud Rate – [7] 115200 Baud
• Parity / Stop Bits – [0] Even Parity, 1 Stop Bit
• Minimum Response Delay - 0.005 sec/5ms
• Maximum Response Delay – 0.1 sec/100ms
2. Repurpose the fan run relay to become a fan interlock for electric heat:
a. Move brown electric heat control wire from LTB2–J to FT terminal 4, wire FR-2 to LTB2J.
b. Add a field wire from LTB2–J to FR terminal 2.
NNootteess:: The following alarms will persist, but the unit will operate:
• Indoor Options Module Communication Status
• Diagnostic: Unit Communications Failure
• Frostat Input
Symbio 700 Configuration and Settings
See “Symbio Service and Installation Mobile Application,” p. 31 for details on editing equipment
configuration. Review and edit the following:
• System Type: CVZT
• Indoor Fan Type: Multi Speed
CCoonnddeennsseerr aanndd AAiirr HHaannddlleerr PPaaiirr WWiirriinngg IInnffoorrmmaattiioonn