RT-SVP07B-EN 15
General Status Display
Unit “Off” or “Stopped”
If at power up the unit is not running, the following display will appear on the Human Interface LCD screen. When this
screen is being displayed, the only functional keys are the six menu keys (Status, Setpoints, Diagnostics, Setup,
Configuration, and Service Mode), the Auto key, the Custom key, and the Stop key.
Unit “On”
If the unit has entered an operating state (running), the following display will appear on the Human Interface LCD screen.
When this screen is being displayed, the only functional keys are the six menu keys (Status, Setpoints, Diagnostics,
Setup, Configuration, and Service Mode), the Auto key, the Custom key, and the Stop key.
Stop by Network Supply Fan ON
Initializing Diagnostics
Used With: Top Status Display
(Shown when unit is off or stopped)
Possible Values:
[see field descriptions at left]Top Left Field:
Unit Off
Unit Stopped
External Stop
Emergency Stop
Stop by Network
Unit Starting
Service Mode Off
Top Right Field:
Supply Fan OFF
Supply Fan ON
Bottom Left Field:
(blank)
Shutdown
Initializing
Freeze Avoidance
Active
Bottom Right Field:
(blank)
(Diagnostics)
VVDA OA Flow 380.0 CCFM Supply Fan ON
Occupied Cool 2 Diagnostics
Used With: Top Status Display
(Shown when unit is on)
Possible Values:
[see field descriptions at left]Top Left Field:
CVZT
VVDA
CVDA
VVZT
Top Middle Field:
(blank)
OA Flow 0 to 500
CCFM
Freeze Avoidance
Top Right Field:
Supply Fan ON
Supply Fan OFF
Bottom Left Field:
(blank)
Occupied
Unoccupied
MorningWU
DaytimeWU
Standby
Shutdown
Occupied TOV
Initializing
Tempering
Rapid Restart
Bottom Middle Field:
(blank)
Heat 1 to 6
Cool 1 to 4
OA Dmpr 0 to 100 %
Dehumid
Purge
Humidify
SA Fan 0 to 100%
Bottom Right Field:
(blank)
Diagnostics