RT-SVP07B-EN 17
General Status Display
Factory Presets
The UCM controlled unit has many operating functions which are preset at the factory, but may be modified to meet the
unique requirements of each job. The following list in Table 2, identifies each of the unit’s adjustable functions and the
value assigned to it. If these factory presets match the application’s requirements, simply press the Auto key at the Human
Interface module to begin unit operation (after completing the Pre-Start and Start-Up procedures in the Installation,
Operation, and Maintenance manual). If the application requires different settings, turn to the listed page beside the
function, press the designated function menu key, then press and hold the Next or Previous key until its screen appears
on the LCD. Once the proper screen appears, simply follow the programming instructions given below the applicable
screen in this manual.
Note: Listed items availability is dependent on unit configuration.)
Table 2. Factory Presets List (Note: Listed Items availability is dependent on unit configuration.
Adjustable Function Factory Preset Changed To
To adjust
press...
General Function
Unit Address (Comm3/Comm4only) 1
___________ Setup
System Mode Auto ___________ Setup
Supply Fan Mode Auto ___________ Setup
Unit Start Delay 0 ___________ Setup
Single Zone VAV Econ Control Enabled ___________ Setup
Single Zone VAV Heat Control Disabled ___________ Setup
Daytime Warm-up Disabled ___________ Setup
Morning Warm-up Enabled ___________ Setup
Morning Warm-up type Cycling ___________ Setup
Supply Air Tempering Disabled ___________ Setup
Unoccupied Mechanical Cooling Enable ___________ Setup
Unoccupied Heating Enable ___________ Setup
Unoccupied Mechanical Cooling Enable ___________ Setup
Unoccupied Heating Enable ___________ Setup
Occupied Dehumidification Enable ___________ Setup
Unoccupied Dehumidification Enable ___________ Setup
Occupied Humidification Disable ___________ Setup
Unoccupied Humidification Disable ___________ Setup
Rapid Restart Economizer Control Disable ___________ Setup
VCM Preheat Output Disable ___________ Setup
Demand Limit Definition - Cooling None ___________ Setup
Demand Limit Definition - Heating None ___________ Setup
Compressor Lead/Lag Enable ___________ Setup
Evap Temperature Limit 35 F ___________ Setup
Coil Frost Cutout Temp 30 F ___________ Setup
Isolation Damper Interlock Disable ___________ Setup
Information Format
Display Text English ___________ Setup
Display Units English ___________ Setup
VAV Control
SA Temp Reset Cool None ___________ Setup