18 RT-SVP07B-EN
General Status Display
Reset Cool Start Temp (Zone/OA) (72/90) ___________ Setup
Reset Cool End Temp (Zone/OA) (69/70) ___________ Setup
Reset Cool Max Amount 5 ___________ Setup
SA Temp Reset Heat None ___________ Setup
Reset Heat Start Temp (Zone/OA) (65/10) ___________ Setup
Reset Heat End Temp (Zone/OA) (68/60) ___________ Setup
Reset Heat Max Amount 10 ___________ Setup
VAV Box Stroke Time 6 Min ___________ Setup
Max Occ. IGV/VFD Command 100 % ___________ Setup
Economizer Control
Economizer Control Enable Type Drybulb ___________ Setup
Unoccupied Economizer Enable ___________ Setup
Head Pressure Control
Sump Drain Relay Control (on power loss) Drain ___________ Setup
Sump Purge Interval Time Disabled ___________ Setup
Sump Purge Duration Time (IPak-I/IPak-II)
1
120/60 sec. ___________ Setup
Sump Water Heater Setpoint 38 F ___________ Setup
Low Limit (Air-cooled/Water-cooled)
1
80/70 deg F ___________ Setup
Upper Limit 120 deg F ___________ Setup
Temporary low limit suppression 20 deg F ___________ Setup
Efficiency check point 105 deg F ___________ Setup
Low amb. control point (Air-cooled/Water-cooled)
1
90/80 deg F ___________ Setup
Alternate Refrigerant Type
1
Disabled ___________ Setup
Sensor Source Selection
Daytime Warm-Up RTM Zone Temp ___________ Setup
Occupied Zone Control RTM Zone Temp ___________ Setup
Unoccupied Zone Control RTM Zone Temp ___________ Setup
Morning Warm-Up RTM Zone Temp ___________ Setup
Space Humidity Control RTM Space Humidity ___________ Setup
Dehumid OVRD Zone Temp RTM Zone Temp ___________ Setup
Zone Reset Function RTM Zone Temp ___________ Setup
Rapid Restart Function ECEM Return Temp ___________ Setup
Monitor RTM Zone Temp ___________ Setup
Outside Air Ventilation
Demand Control Ventilation Disable ___________ Setup
Active/Passive DCV Control Passive ___________ Setup
OA Flow Compensation Enabled ___________ Setup
OA Flow C02 Reset (IPak-INon-DCV) Disabled ___________ Setup
CO2 Start (IPak-I Non-DCV) 800 ___________ Setup
CO2 Max (IPak-I Non-DCV) 1000 ___________ Setup
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
Adjustable Function Factory Preset Changed To
To adjust
press...