General Status Display
Cond Fan VFD Ckt-2 (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
0 VDC ___________ Setup
Modulating Gas Heat Actuator (if equipped)
Actuator Setup
Direct
1
/Reverse
1
___________ Setup
Max Stroke Time
90 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
2 VDC
2
/5 VDC
1
___________ Setup
Outdoor Air Bypass Damper (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
2 VDC ___________ Setup
Exhaust Bypass Damper (if equipped)
Actuator Setup
Direct ___________ Setup
Max Stroke Time
60 sec ___________ Setup
Max Voltage
10 VDC ___________ Setup
Min Voltage
2 VDC ___________ Setup
Control Algorithm Tuning Parameters
(Partial)
1
Zone Control Occupied Heating Proportional Gain
IPak I Gas
30.0 deg F ___________ Setup
IPak I Electric
45.0 deg F ___________ Setup
IPak II Gas
30.0 deg F ___________ Setup
IPak II Electric-90 kw
45.0 deg F ___________ Setup
IPak II Electric -140 kw
60.0 deg F ___________ Setup
IPak II Electric-265 kw
75.0 deg F ___________ Setup
IPak II Electric-300 kw
75.0 deg F ___________ Setup
CV Air Economizer Control Gains
Proportional
10.0 % F ___________ Setup
Reset Time
DISABLE ___________ Setup
Rate Time
0 Sec ___________ Setup
Bias
0 deg F ___________ Setup
SZVAV Cooling Control Gains
Proportional
6.0 % F ___________ Setup
Reset Time
1200 Sec ___________ Setup
Rate Time
0 Sec ___________ Setup
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
Adjustable Function Factory Preset Changed To
To adjust
press...