Unit Startup
RT-SVX24J-EN 149
130-162 Ton Low CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45
CFM
Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T
23000 1.82 1.27 1.06 1.27 0.96 1.05 0.91 1.02 0.89 0.87 0.67 0.65 0.62 0.57 0.51 0.44 0.39
26000 2.31 1.60 1.33 1.60 1.21 1.32 1.14 1.28 1.11 1.09 0.83 0.81 0.77 0.71 0.63 0.54 0.47
30000 2.10 1.74 2.09 1.57 1.71 1.49 1.67 1.44 1.41 1.06 1.03 0.98 0.90 0.79 0.69 0.59
35000 2.80 2.32 2.79 2.09 2.28 1.97 2.22 1.91 1.87 1.39 1.36 1.29 1.18 1.03 0.88 0.75
40000 ————2.97 2.68 2.92 2.52 2.84 2.45 2.39 1.77 1.72 1.62 1.48 1.29 1.10 0.92
45000 ———————————2.96 2.17 2.11 1.99 1.81 1.57 1.33 1.10
50000 ————————————2.62 2.54 2.39 2.17 1.87 1.57 1.30
55000 ————————————3.09 3.00 2.82 2.56 2.20 1.83 1.50
58000 ————————————3.40 3.29 3.10 2.80 2.40 1.99 1.62
Standard CFM ERW — 90-162 Tons
90/100 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45 50
CFM
Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T
16000 1.26 0.84 1.49 0.68 1.02 0.61 0.81 0.57 0.61 0.55 0.60 0.43 0.42 0.40 0.38 0.35 0.32 0.29 0.17
20000 1.95 1.30 2.30 1.05 1.57 0.93 1.24 0.88 0.93 0.85 0.92 0.64 0.63 0.61 0.57 0.52 0.48 0.43 0.25
25000 2.00 1.62 2.42 1.43 1.90 1.34 1.42 1.30 1.41 0.97 0.95 0.92 0.86 0.79 0.71 0.64 0.35
30000 2.84 2.28 2.02 2.69 1.89 1.99 1.82 1.97 1.35 1.32 1.27 1.19 1.08 0.97 0.87 0.46
33000 2.74 2.42 2.26 2.38 2.18 2.36 1.61 1.58 1.51 1.42 1.29 1.16 1.03 0.53
36000 2.86 2.67 2.81 2.57 2.78 1.89 1.85 1.77 1.66 1.50 1.35 1.20
40000 2.28 2.23 2.14 2.00 1.81 1.61 1.44
105/118 Ton Standard CFM ERW - Field measured plenum pressure (inches wc)
OA Actuator Reading [Degrees] RA Actuator Reading [Degrees]
60 50 40 30 20 10 0 10 20 30 35 40 45 50
CFM
Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ Econ TRAQ E/T E/T E/T E/T E/T E/T E/T E/T
19000 1.76 1.17 2.07 0.95 1.42 0.84 1.12 0.79 0.84 0.76 0.83 0.58 0.57 0.55 0.52 0.47 0.43 0.39 0.22
23000 2.55 1.69 1.36 2.05 1.21 1.61 1.13 1.20 1.09 1.19 0.82 0.80 0.77 0.73 0.66 0.60 0.54 0.30
28000 2.47 1.99 3.00 1.76 2.34 1.64 1.73 1.59 1.72 1.18 1.15 1.11 1.04 0.94 0.85 0.76 0.40
33000 2.72 2.40 2.24 2.36 2.16 2.34 1.59 1.55 1.49 1.39 1.26 1.13 1.01
38000 2.92 2.82 2.05 2.01 1.92 1.80 1.62 1.45 1.29
43000 2.57 2.51 2.41 2.24 2.02 1.80 1.59
45000 2.80 2.73 2.62 2.44 2.19 1.95 1.73
continued on next page
Table 44. Standard units with ERW field measured plenum pressure (continued)