Service and Maintenance
RT-SVX24J-EN 175
Hz (right) 150F 175F
Low (25") High (262.5 kW) Downflow 215F 155F
Hz (right) 235F 155F
Low (90 kW) Downflow 150F 175F
Hz (right) 150F 175F
Table 52. Electric Heat—Selection Limits
Table 53. Compressor Circuit Breaker Electrical Characteristics
460V 575V 380V
Unit Size
Compressor
Designator
Compressor
Size
Must
Hold
Must
Trip
Must
Hold
Must
Trip
Must
Hold
Must
Trip
90/105 1A, 2A CSHN250 41.5 47.7 33.2 38.2 41.4 47.6
1B, 2B CSHN250 41.5 47.7 33.2 38.2 41.4 47.6
105/118 1A, 2A CSHN250 41.5 47.7 33.2 38.2 41.4 47.6
1B, 2B CSHN315 54.4 62.6 43.6 50.1 54.3 62.4
120/128 1A, 2A CSHN315 57.7 66.4 46.3 53.2 57.3 66
1B, 2B CSHN315 54.4 62.6 43.6 50.1 54.3 62.4
130/140 1A, 2A CSHN315 57.7 66.4 46.3 53.2 57.3 66
1B, 2B CSHN374 63.4 72.9 50.0 57.5 63.3 72.8
150/162 1A, 2A CSHN374 66.7 76.7 52.7 60.6 66.4 76.3
1B, 2B CSHN374 63.4 72.9 50.0 57.5 63.3 72.8