Installation
78 RT-SVX24J-EN
Figure 55. Typical field power wiring
Figure 56.Customer connection wire range
Note: Non-fused disconnect switch size is
calculated by selecting the size
greater than or equal to 1.15 X (sum of
unit loads). See unit literature for unit
load values. (See following page for
circuit breaker sizing)