Checkout Procedure Measurement
Expected Value
Step 1
Measure AC voltage across the current
input.
Vac 0.0 V
AC voltage will affect further
measurement.
Step 2
Measure DC voltage across the current
input.
Vdc 0.0 V
Step 3
Measure the DC current across the
current input.
Compare the measured current with
the expected value based on the
manufacturer’s specification and
current conditions.
Binary Inputs, 24 Vac Detect
Checkout Procedure Measurement
Expected Value
Step 1
Measure AC voltage across the
resistive termination.
Vac 0.0 V
AC voltage will affect further
measurement.
Step 2
Measure DC voltage across the
resistive termination.
Vdc 0.0 V
DC voltage will affect further
measurements.
Step 3
Measure the resistance across the
resistive termination.