Trane Symbio 700 - For Heat Pump Units in Active Mechanical Heating and Outdoor Air Temperature ≥ 0°F; Circuit X Low Pressure Lockout (Manual Reset)

Trane Symbio 700
210 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
For Heat Pump Units in Active Mechanical Heating and Outdoor Air Temperature ≥ 0°F
If a compressor low pressure cutout input opens:
All Compressor Outputs on the effected circuit will be immediately Commanded OFF.
The “Circuit X LPC Trip” diagnostic point will be annunciated.
The Circuit will be disabled for 3 minutes.
The Circuit’s LPC trip count will be incremented.
On Heat Pumps, if the Outdoor Air Temperature is < 0°F or if the unit is in active Defrost, the low
pressure cutout diagnostic is ignored. This is to allow a heat pump to continue to provide heating
capacity at low ambient conditions.
After the 3 minute low pressure event timeout has expired, if the unit is not under a “Circuit Lockout”
event:
The “Circuit X LPC Trip” diagnostic will be reset
If the cooling stage is still requested ON, the circuit will be allowed to stage again.
If the Circuit runs for 3 minutes, its LPC Trip Count will be reset to 0.
Circuit “X” Low Pressure Lockout (Manual Reset)
If a compressor/circuit accumulates 4 “Circuit X Low Pressure Trips” without the circuit running for the
3-minute minimum on time (counter is not reset), a “Circuit X LPC Lockout” will be generated.
Once the lockout is generated the circuit will be locked out until a Diagnostic Reset is initiated.