58
Zone Sensor Mode
Volts DC
+- 5%
Ohms
Rx1K
System
Switch
Fan
switch
0.00 0.00 Short Short
0.47 2.32 OFF AUTO
0.82 4.87 COOL AUTO
1.09 7.68 AUTO AUTO
1.30 10.77 OFF ON
1.43 13.32 COOL ON
1.54 16.13 AUTO ON
1.65 19.48 HEAT AUTO
1.84 27.93 HEAT ON
1.94 35.00 EM HEAT AUTO
2.03 43.45 EM HEAT ON
2.50 Open
circuit
Open
circuit
Zone Sensor Setpoint
°F °C (K ohms) DCV
90 32.22 0.1106 0.249
89 31.67 0.1301 0.288
88 31.11 0.1495 0.325
87 30.56 0.1689 0.362
86 30.00 0.1884 0.397
85 29.44 0.2079 0.430
84 28.89 0.2273 0.463
83 28.33 0.2468 0.495
82 27.78 0.2663 0.526
81 27.22 0.2858 0.556
80 26.67 0.3053 0.585
79 26.11 0.3247 0.613
78 25.56 0.3442 0.640
77 25.00 0.3637 0.667
76 24.44 0.3832 0.693
75 23.89 0.4026 0.718
74 23.33 0.4221 0.742
°F °C (K ohms) DCV
73 22.78 0.4416 0.766
72 22.22 0.4610 0.789
71 21.67 0.4805 0.812
70 21.11 0.5000 0.834
69 20.56 0.5195 0.855
68 20.00 0.5390 0.876
67 19.44 0.5584 0.896
66 18.89 0.5779 0.916
65 18.33 0.5974 0.935
64 17.78 0.6169 0.954
63 17.22 0.6363 0.972
62 16.67 0.6558 0.990
61 16.11 0.6753 1.008
60 15.56 0.6948 1.025
59 15.00 0.7142 1.042
58 14.44 0.7337 1.058
57 13.89 0.7544 1.075
56 13.33 0.7751 1.092
55 12.78 0.7958 1.108
54 12.22 0.8166 1.124
53 11.67 0.8373 1.139
52 11.11 0.8580 1.155
51 10.56 0.8787 1.169
50 10.00 0.8994 1.184
49 9.44 0.9179 1.197
48 8.89 0.9363 1.209
47 8.33 0.9548 1.221
46 7.78 0.9733 1.233
45 7.22 0.9918 1.245
44 6.67 1.0102 1.257
43 6.11 1.0287 1.268
42 5.56 1.0472 1.279
41 5.00 1.0656 1.290
40 4.44 1.0841 1.301