CNT-SVX09E-EN 15
Network Variable Bindings
nvoBIP1Status SNVT_switch Universal Input 1 Status Output:
• Indicates the value of universal input 1 if it is configured
as binary.
• If universal input 1 is not configured as binary, this output
is
invalid
.
nvoBIP2Status SNVT_switch Universal Input 2 Status Output:
• Indicates the value of universal input 2 if it is configured
as binary.
• If universal input 2 is not configured as binary, this output
is
invalid
.
nvoBIP3Status SNVT_switch Universal Input 3 Status Output:
• Indicates the value of universal input 3 if it is configured
as binary.
• If universal input 3 is not configured as binary, this output
is
invalid
.
nvoBIP4Status SNVT_switch Universal Input 4 Status Output:
• Indicates the value of universal input 4 if it is configured
as binary.
• If universal input 4 is not configured as binary, this output
is
invalid
.
nvoCurrent1 SNVT_amp_mil Universal Input 1 Status Output:
• Indicates the value of universal input 1 if it is configured
as 0–20 mA.
• If universal input 1 is not configured as 0–20 mA, this
o
ut
put is -3276.8.
nvoCurrent2 SNVT_amp_mil Universal Input 2 Status Output:
• Indicates the value of universal input 2 if it is configured
as 0–20 mA.
• If universal input 2 is not configured as 0–20 mA, this
o
ut
put is -3276.8.
nvoCurrent3 SNVT_amp_mil Universal Input 3 Status Output:
Indicates the value of universal input 3 if it is configured as
0–20 mA.
If universal input 3 is not configured as 0–20 mA, this output
is
-3
276.8.
nvoCurrent4 SNVT_amp_mil Universal Input 4 Status Output:
• Indicates the value of universal input 4 if it is configured
as 0–20 mA.
• If universal input 4 is not configured as 0–20 mA, this
o
ut
put is -3276.8.
nvoVolts1 SNVT_volt Universal Input 1 Status Output:
• Indicates the value of universal input 1 if it is configured
as 0–10 Vdc.
• If universal input 1 is not configured as 0–10 Vdc, this
o
ut
put is -3276.8.
nvoVolts2 SNVT_volt Universal Input 2 Status Output:
• Indicates the value of universal input 2 if it is configured
as 0–10 Vdc.
• If universal input 2 is not configured as 0–10 Vdc, this
o
ut
put is -3276.8.
nvoVolts3 SNVT_volt Universal Input 3 Status Output:
• Indicates the value of universal input 3 if it is configured
as 0–10 Vdc.
• If universal input 3 is not configured as 0–10 Vdc, this
o
ut
put is -3276.8.
Table 2. Tracer MP503 network variable outputs (continued)
Variable name Data type Description