Resetting Chiller Failures
BMTX-SVU01B-EN 209
Figure 43. Chiller Plant Control Status System Screen
Resetting Chiller Failures
You can reset all failures or an individual chiller failure.
Resetting an Individual Chiller Failure
1. From the Status menu, select Chiller Plant Control Status. The
Chiller Plant Control Status System screen displays. If a failure
exists, the message “Failure Exists” displays in red in the Operating
Mode field.
2. Click the Chillers tab (see Figure 44 on page 210).