Forcing a Chiller to be Added
BMTX-SVU01B-EN 213
Forcing a Chiller to be Added
1. From the Status menu, select Chiller Plant Control Status. The
Chiller Plant Control Status System screen displays.
2. Click Force Add (this button will be active only if chillers are avail-
able to be added). A warning dialog box displays (see Figure 49). This
message explains which chiller is about to be added and forces you to
confirm the add should take place.
Figure 49. Force Add Warning
3. Click Yes to add a chiller. The Chiller Plant Control Status System
screen displays again.
Forcing a Chiller to be Subtracted
1. From the Status menu, select Chiller Plant Control Status. The
Chiller Plant Control Status System screen displays.
2. Click the down arrow of the scroll bar to display the Force Subtract
button (this button will be active only if chillers are available to be
subtracted).
3. Click Force Subtract. A warning message displays (see Figure 50).
This message explains which chiller is about to be subtracted and
forces you to confirm the subtract should take place.
Figure 50. Force Subtract Warning
4. Click Yes to subtract a chiller. The Chiller Plant Control Status Sys-
tem screen displays again.