Forcing the Chiller Sequence to be Rotated
BMTX-SVU01B-EN 215
Forcing the Chiller Sequence to be
Rotated
The Chiller Plant Control Sequence Numbers screen displays the current
rotation sequence of all chillers that have a rotation type of normal. Base,
peak, and swing chillers do not appear on this display. You can rotate the
sequence of chillers by selecting the Rotate button, or by manually
reshuffling the sequence by using the New Sequence Number up and
down arrows (see Figure 51).
Figure 51. Chiller Plant Control Sequence Numbers
To rotate sequence numbers:
1. From the Status menu, select Chiller Plant Control Status. The
Chiller Plant Control Status System screen displays.
2. Click the Chillers tab to display the Chillers screen.
3. Click the down arrow on the right side of the screen to display the
Change Sequence Numbers button (see Figure 52 on page 216).
Note:
Tracer Summit does not allow duplicate or missing sequence
numbers. Removing a chiller from the member list could create
a missing sequence number. In this case, you must re-order the
sequence numbers.