Displaying and Changing Status Information
58 BMTX-SVU01B-EN
Setting Up the Simplified Override
Dialog Box
With the Simplified Override dialog box, the daily operator can change
the present value of a property without having to select the priority level.
by right-clicking on a property in a graphic. This eliminates the need to
access the editor to override the present value. The Simplified Override
dialog box must first be setup before it is available for use in Tracer Sum-
mit.
To set up the simplified override dialog box:
1. From the Site Security editor, click the Functions tab.
2. In the Access column, click the checkbox for the following functions
(see Figure 49):
Change Values from Graphics
User – Any Priority Level Point Control (select one of the options)
3. In the Select Default Priority for Simplified Override Dialog drop-
down, select a user default priority level.
Figure 49. Functions tab
Note:
The highest user priority level you select will determine the
highest user level default override setting available.