Using the Simplified Override Dialog Box
BMTX-SVU01B-EN 67
4. Click the Apply button to apply the override and view the results, or
click OK to apply the changes and close the dialog box.
To return control back to the BAS, see “Releasing Control Back to the Sys-
tem” on page 71.
Overriding a Binary Output or a Lighting Value
1. Open the Simplified Override dialog as described in “Accessing the
Simplified Override Dialog box” on page 60. The override dialog box
displays (see Figure 59).
Figure 59. Binary Output Override dialog box
2. Click on the Manual option in the Auto/Manual knob.
Note:
Click on the More control button at the bottom of the dialog box
to display the Priority Arrays box. To perform an override, your
default control priority level must be higher than priority level
listed in the box. If not, refer to “Using the Advanced Systems
Override” on page 72.