XM30 and XM32 Module Power Requirements
The XM30 and XM32 expansion modules are DC powered, typically through the use of an IMC
link. The XM70/XM90 is AC powered and can power up to two additional devices (see
“Communication Wiring Examples,” p. 15.)
Table 7. Expansion module power input and power draw
Module
Power Input Power Draw (mA)
XM30 expansion module
24 Vdc 120
XM32 expansion module
24 Vdc 100
XM70 expansion module
24 Vac
26 VA plus a maximum of 12 VA for each binary output
XM90 expansion module
24 Vac
60 VA plus a maximum of 12 VA for each binary output