BAS-SVX46E-EN
25
Figure 16. Possible expansion module errors (Tracer TU)
EErrrroorr:: DDuupplliiccaattee rroottaarryy sswwiittcchh sseettttiinnggss ddeetteecctteedd
Another expansion module with the same rotary switch setting is present on the IMC link.
SSoolluuttiioonn: Change the incorrectly addressed module to match its configuration.
1. Navigate to the UUttiilliittiieess//CCoonnttrroolllleerr//CCoonnttrroolllleerr SSeettttiinnggss screen.
2. Using the configurations shown in the Expansion Module Status frame, visually verify that all
modules have been addressed correctly. When the improperly addressed module is found,
readdress the module to match the configured address.
3. Navigate to the UUttiilliittiieess//SSttaattuuss//CCoonnttrroolllleerr SSeettttiinnggss screen; click SSeenndd ttoo DDeevviiccee..
4. Verify that Error has cleared from list.
EErrrroorr:: DDiissccoovveerreedd aa ddeevviiccee tthhaatt iiss nnoott ccoonnffiigguurreedd
PPrroobblleemm: An expansion module was discovered on the IMC link that was not configured.
SSoolluuttiioonn: configure the module (see “Configuring the Expansion Modules,” p. 22).
NNoottee:: An un-configured module will not cause communication issues; however, it will not have
referencing capability.
EErrrroorr:: WWrroonngg hhaarrddwwaarree ppaarrtt nnuummbbeerr
PPrroobblleemm: An expansion module was discovered on the IMC link that was not configured.
SSoolluuttiioonn: Reconfigure the module in the Utilities/Status/Controller Settings screen to match the
hardware configuration or replace the device with the correct hardware (XM module).
EErrrroorr:: XXMM wwiitthh tthhiiss rroottaarryy sswwiittcchh sseettttiinngg wwaass nnoott ffoouunndd
PPrroobblleemm: A configured module was not found on the IMC link. This could be caused by one of
the following:
Module is now powered.
The remote mounted communication link is not connected.
The rotary address on the expansion module was incorrectly set.
SSoolluuttiioonn: Apply power to the module (if applicable), correct the remote communication on the
link, or re-address the module to match the configuration.