Table 2. XM30 device connections
Connection
Quantity Types Range
Inputs
4 total
Can be configured using any combination of analog
or binary inputs/analog outputs
Thermistor
2252Ω, 10k, 20k, 100kΩ
Resistive (Setpoint)
100Ω to 1
RTD
1 kΩ; platinum, Balco™ or nickel
Current
0 to 20 mA (linear)
Voltage 0 to 10 Vdc (linear)
Binary Dry Contact
Pulse Accumulator
Minimum 20 milliseconds open or
closed
Outputs
Current
0 to 20 mA @ 16V
Voltage
0 to 16 Vdc @ 20mA
Table 3. XM32 device connections
Connection
Quantity Types Range
Notes
Binary output (BO1 to
BO4)
4
General purpose 10 A; up to 277 Vac
Power must be wired to the binary
output. All outputs are isolated
from each other, and from ground
or power.
Ranges given are per contact
Motor
1/3 hp@125 Vac or 1/2
hp@277
Pilot duty (inductive load) 2 A; up to 125 Vac
Resistive load
8 A; up to 250 Vac or
10 A; up to 30 Vac or
10 A; up to 30 Vdc