INSTINCT NATURAL TO PROPANE CONVERSION INSTRUCTIONS
Table 1: Combustion Settings
Propane (All Models)
High Fire
CO
2
Range 10.4 - 11.0%
O
2
Range 5.1 - 4.2%
CO Max 200 ppm
Low Fire
CO
2
Range 10.4 - 11.0%
Ensure CO
2
values measured are less than or equal to
High Fire CO
2
measurements
O
2
Range 5.1 - 4.2%
Ensure O
2
values measured are higher than or equal to
High Fire O
2
measurements
CO Max 10 ppm