UPS Input Voltage | 156V~276V Single Phase |
---|---|
Transformer Input Voltage | 200/208/220/230/240V |
Input Frequency | 50/60 Hz ± 3 Hz |
Input Current | 22.6A |
Inrush Current | <150A |
Power Factor (Full Load) | >0.97 |
Efficiency (Full Load/On-Line) | >87% |
UPS Circuit Breaker | 40A |
Transformer Circuit Breaker | 40A (2 pole) |
VA | 6000 |
---|---|
Watts (Power Factor: 0.7) | 4200 |
Waveform (On-Line) | Sinewave |
Waveform (On-Battery) | Sinewave |
Output Voltage (RMS) | 120/200/208/220/230/240V |
Output Frequency | 50/60 Hz (± 0.2 Hz on battery) |
Voltage Regulation | ±3% |
Max. Harmonic Distortion (Linear Full Load) | <3% |
Max. Harmonic Distortion (Non-Linear Full Load) | <6% |
Overload Capabilities | 102% (continuous), 102%~125% (1 min.), 125%~150% (30 sec.), 150% (Immediate) |
Short Circuit Capability | 90A |
Crest Factor | 3:1 |
On-Line Transfer Time (Line to Battery, Battery to Line) | 0 ms |
---|---|
Audible Noise (Full Load @ 1 m) | <50 dBA |
Typical Backup Time (Single Battery Pack, Full Load) | 10 min. |
Typical Backup Time (Single Battery Pack, Half Load) | 25 min. |
Dimensions (H × D × W) | 5[1]/8 × 17½ × 22½ in. (13 × 45 × 58 cm) |
---|---|
Net Weight (UPS) | 42 lb. (19.1 kg) |
Net Weight (Transformer) | 120 lb. (54.5 kg) |
Net Weight (Battery Pack) | 170 lb. (77.3 kg) |
UPS Input Voltage | 156V~276V Single Phase |
---|---|
Transformer Input Voltage | 200/208/220/230/240V |
Input Frequency | 50/60 Hz ± 3 Hz |
Input Current | 40A |
Inrush Current | <200A |
Power Factor (Full Load) | >0.97 |
Efficiency (Full Load/On-Line) | >88% |
UPS Circuit Breaker | 63A |
Transformer Circuit Breaker | 63A (2 pole) |
VA | 10000 |
---|---|
Watts (Power Factor: 0.7) | 7000 |
Waveform (On-Line) | Sinewave |
Waveform (On-Battery) | Sinewave |
Output Voltage (RMS) | 120/200/208/220/230/240V |
Output Frequency | 50/60 Hz (± 0.2 Hz on battery) |
Voltage Regulation | ±3% |
Max. Harmonic Distortion (Linear Full Load) | <3% |
Max. Harmonic Distortion (Non-Linear Full Load) | <6% |
Overload Capabilities | 102% (continuous), 102%~125% (1 min.), 125%~150% (30 sec.), >150% (Immediate) |
Short Circuit Capability | 160A |
Crest Factor | 3:1 |
On-Line Transfer Time (Line to Battery, Battery to Line) | 0 ms |
---|---|
Audible Noise (Full Load @ 1 m) | <55 dBA |
Typical Backup Time (Single Battery Pack, Full Load) | 6 min. |
Typical Backup Time (Single Battery Pack, Half Load) | 15 min. |
Dimensions (H × D × W) | 5[1]/8 × 17½ × 22½ in. (13 × 45 × 58 cm) |
---|---|
Net Weight (UPS) | 53 lb. (24.1 kg) |
Net Weight (Transformer) | 120 lb. (54.5 kg) |
Net Weight (Battery Pack) | 170 lb. (77.3 kg) |
Guidelines for properly placing the UPS to ensure safe operation and optimal performance.
Precautions for connecting the UPS power supply, ensuring it's single phase and grounded.
Warnings against using UPS in life support and grounding requirements for UPS and transformers.
Notes that UPS, transformer, and battery packs require no routine maintenance and should not be opened.
Critical safety instructions for handling and replacing UPS batteries, including handling risks and disposal.
Procedure for installing a single unit in a 4-post rack enclosure using included shelves.
Steps for installing two UPS units back-to-back in a 4-post rack using shelf kits.
Instructions for mounting equipment in a 2-post rack using provided shelf kits.
Guidance on using plastic feet and extensions to tower mount the UPS, battery pack, and transformer.
Details the location and function of the UPS front panel controls and indicators.
Diagram and description of connectors and components on the UPS rear panel.
Diagram and description of connectors and components on the Isolation Transformer rear panel.
Diagram and description of connectors and components on the Battery Pack rear panel.
Detailed explanation of each port and connector on the UPS rear panel.
Detailed explanation of each port and connector on the Isolation Transformer rear panel.
Detailed explanation of each port and connector on the Battery Pack rear panel.
Guidelines for qualified electricians on hardwiring UPS input/output and cable requirements.
Steps for hardwiring the utility power source to the UPS input and UPS output to equipment.
Steps for connecting the transformer to the UPS and equipment, and setting input voltage.
Instructions for connecting external battery packs and communication cables to the UPS.
Procedure for turning on the UPS input and starting inverter operation, including cold start.
Steps to configure UPS output voltage, frequency, and operating modes (Economy/On-line).
Instructions to turn on the UPS output and set the transformer bypass switch to NORMAL.
Procedure for safely powering down the UPS and transformer, including circuit breaker actions.
Description of the UPS startup self-test sequence and results displayed on the LCD.
Error messages displayed during a failed self-test and contact information for technical support.
Explanation of different operating modes (Online, Economy, On Battery, Bypass) and LCD display readings.
Details on the UPS audible alarms when operating on battery power and how to silence them.
How the UPS displays overload conditions and the countdown durations for overload protection.
Messages displayed when the UPS is in bypass mode due to voltage deviations.
Conditions that trigger UPS shutdown and the corresponding LCD display messages.
Details the terms and conditions of the 2-year limited warranty for Tripp Lite products.
Information on the Ultimate Lifetime Insurance Policy for connected equipment damage.
Table comparing specifications for SU6000RT3U and SU10KRT3U models.
Technical input specifications including voltage, frequency, current, and circuit breakers.
Technical output specifications including VA, Watts, waveform, voltage regulation, and overload capabilities.
Operational specifications like transfer time, audible noise, and backup time.
List of indicators, including LCD display and LEDs on the UPS.
Details on communication ports like RS-232, dry contact, and accessory slot.
Physical dimensions and weight specifications for the UPS, transformer, and battery pack.