Commissioning
Commissioning the device in EtherNet/IP
84
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
IO-Link Port Class (VSC 179)
This class provides one instance per IO-Link port at the IO-Link master module.
Attr. no. Designation Get/
set
Type Meaning
Dec. Hex.
Parameters
1 0x01 Operation mode G/S USINT 0 = IO-Link without validation
1 = IO-Link with family compatible
device
2 = IO-Link with compatible device
3 = IO-Link with identical device
4 = DI (with parameter access)
5…7 = reserved
8 = DI 8 = DI
2 0x02 Data Storage Mode G/S USINT 0 = activated
1 = overwrite
2 = read in
3 = deactivated, clear
3 0x03 Cycle time G/S USINT See [}100]
4 0x04 Revision G/S USINT 0 = automatic
1 = V 1.0
5 0x05 Activate Quick
Start-Up
G/S USINT 0 = no
1 = yes
6 0x06 Device parameteriza-
tion via GSD
G/S USINT 0 = no
1 = yes
7 0x07 Process input data
invalid
G/S USINT 0 = diagnostics generated
1 = no diagnostic generated
8 0x08 Deactivate
diagnostics
G/S USINT 0 = no
1 = notifications
2 = notifications and warnings
3 = yes
9 0x09 Process input data
mapping
G/S USINT 0 = direct
1 = swap16 bit
2 = swap 32 bit
3 = swap all
10 0x0A Process output data
mapping
G/S USINT 0 = direct
1 = swap16 bit
2 = swap 32 bit
3 = swap all
11 0x0B Vendor ID G/S INT
12 0x0C Device ID G/S DINT
Diagnostics
13 0x0D Wrong or
missing device
G USINT 0 = inactive
1 = active
14 0x0E Data storage
error
G USINT 0 = inactive
1 = active
15 0x0F Process input data
invalid
G USINT 0 = inactive
1 = active