Do not wait for an emergency to learn how to connect your generator and
select loads to GenerLink™. (See Setup Procedures for detailed information.)
■
Do not connect the GenerLok™ power cord to GenerLink™ if the red
fault status light is continuously illuminated.
■
Never connect or disconnect the GenerLok™ power cord to/from your
portable generator while the generator is operating. Turn off the portable
generator and turn off all circuits in your breaker panel before connecting
or disconnecting the power cord.
■
Before using the GenerLok™ power cord, check the cord for exposed wires
and/or frayed insulation.
■
Keep the power cord stored in a dry, safe location when not in use.
■
Ensure that the GenerLok™ power cord is in a protected area where it will
not be damaged by lawn mowers, power tools or vehicles.
■
Never attempt to remove, repair, dismantle, modify, or alter GenerLink™
once it has been installed.
!
CAUTION
Always locate and operate your
generator in accordance with the
manufacturer’s instructions as outlines
in the generator owner’s manual.
10 15
SAMPLE WORKSHEET
Generator Size: (Watts)
Load Start X Run Watts = Load
Factor Watts
Refrigerator
3
X
1000
=
3000
Sump Pump
2
X
1000
=
2000
Computer
1
X
200
=
200
Fan (central)
¹₄
hp
3
X
400
=
1200
X
=
X
=
60
X
5
=
300
100
X
1
=
100
150
X
0
=
0
Total:
6800
BCDE
Lights Wattage Number
F
G
9600