Do not wait for an emergency to learn how to connect your generator and
select loads to GenerLink. (See Setup Procedures for detailed information.)
Do not connect the GenerLok power cord to GenerLink if the red
fault status light is continuously illuminated.
Never connect or disconnect the GenerLok power cord to/from your
portable generator while the generator is operating. Turn off the portable
generator and turn off all circuits in your breaker panel before connecting
or disconnecting the power cord.
Before using the GenerLok power cord, check the cord for exposed wires
and/or frayed insulation.
Keep the power cord stored in a dry, safe location when not in use.
Ensure that the GenerLok power cord is in a protected area where it will
not be damaged by lawn mowers, power tools or vehicles.
Never attempt to remove, repair, dismantle, modify, or alter GenerLink
once it has been installed.
!
CAUTION
Always locate and operate your
generator in accordance with the
manufacturer’s instructions as outlines
in the generator owners manual.
10 15
SAMPLE WORKSHEET
Generator Size: (Watts)
Load Start X Run Watts = Load
Factor Watts
Refrigerator
3
X
1000
=
3000
Sump Pump
2
X
1000
=
2000
Computer
1
X
200
=
200
Fan (central)
¹₄
hp
3
X
400
=
1200
X
=
X
=
60
X
5
=
300
100
X
1
=
100
150
X
0
=
0
Total:
6800
BCDE
Lights Wattage Number
F
G
9600