29
Instructions for the installer
Layout of the electrical connections for zone control systems
Note: The terminal connections 3 and 4 indica-
ted in the diagram refer to the valve’s in-
ternal limit stop, when the same valve is
in the “low temperature” position.
The microswitch on the 3-way valve closes whilst the room
thermostat is demanding heat when the diverter valve
reaches the “low temperature” position and sends the
request to the boiler.
The 3-way valve has to use the limit switch contact in order
to simulate this type of request.
When the thermostat’s contact (On-Off) is closed, the 3-
way valve opens the high temperature zone and closes the
low temperature zone (controlled by the digital room
controller “Regolafacile”).
With the thermostat’s contact (On-Off) open, the 3-way valve
deviates towards the low temperature zone (the
temperature value can be adjusted with the digital room
controller).
M
3
L
N
TA
4
LT zone
HT zone
Flow
Return
External voltage line
To the terminals 3 and 4 on the Y2 connector
M
3
LT z o ne
HT zone
Flow
Retur