Instructions for the installer
MODULATING PUMP MINIMUM MODULATION LEVEL
Continue to change to the parameters by pressing the – key
(decrease).
The successive parameter which can be changed is:
MODULATING PUMP MINIMUM MODULATION LEVEL (PL).
Repeat the operations A-B-C for setting the desired value
from 0 to 99%.
Standard setting: 19 % per ALKON 50
25 % per ALKON 70
A
Z
Z
U
R
R
O
V
I
O
L
A
G
I
A
L
L
O
B
L
U
MODULATING PUMP MODULATING CAPACITY
Continue to change the parameters by pressing the – key
(decrease).
The successive parameter which can be changed is:
MODULATING PUMP MODULATING CAPACITY (Pr).
A
Z
Z
U
R
R
O
V
I
O
L
A
G
I
A
L
L
O
B
L
U
Repeat the operations A-B-C for setting the desired value
from 20 to 99%.
Standard setting: 99%
SETTING OF THE MINIMUM HEATING TEMPERATURE
Continue to change to the parameters by pressing the – key
(decrease).
The successive parameter which can be changed is: SETTING
OF THE MINIMUM HEATING TEMPERATURE (HL).
A
Z
Z
U
R
R
O
V
I
O
L
A
G
I
A
L
L
O
B
L
U
Repeat the operations A-B-C for setting the desired value
from 20 to 60°C
Standard setting: 35°C
SETTING OF THE MAXIMUM HEATING TEMPERATU-
RE
Continue to change to the parameters by pressing the – key
(decrease).
The successive parameter which can be changed is: SETTING
OF THE MAXIMUM HEATING TEMPERATURE (HH
A
Z
Z
U
R
R
O
V
I
O
L
A
G
I
A
L
L
O
B
L
U
Repeat the operations A-B-C for setting the desired value
from 65 to 85°C
Standard setting: 80°C
A
Z
Z
U
R
R
O
V
I
O
L
A
G
I
A
L
L
O
B
L
U
A
Z
Z
U
R
R
O
V
I
O
L
A
G
I
A
L
L
O
B
L
U
SETTING OF THE MINIMUM DHW TEMPERATURE (only
if combined with an external storage tank)
Continue to change to the parameters by pressing the – key
(decrease).
The successive parameter which can be changed is: SETTING
OF THE MINIMUM DHW TEMPERATURE (dL).
Repeat the operations A-B-C for setting the desired value
from 35 to 45°C
Standard setting: 40°C
SETTING OF THE MAXIMUM DHW TEMPERATURE
(only if combined with an external storage tank)
Continue to change to the parameters by pressing the – key
(decrease).
The successive parameter which can be changed is: SETTING
OF THE MAXIMUM DHW TEMPERATURE (dH).
Repeat the operations A-B-C for setting the desired value
from 50 to 65°C
Standard setting: 60°C.