2. Limitations for ambient temperature up to 55°C, maximum system output current 45
Amps:
Maximum load per circuit breakers rated:1 A, 4 A, 5 A, 7.5 A, 10 A, 15 A, 20 A and 25 A
is 80% of their nominal rate.
Maximum load per circuit breaker rated 30 A is 60% of its nominal rate.
3. Limitations for ambient temperature up to 75°C, maximum system output current 28
Amps:
Maximum load per circuit breakers rated:1 A, 4 A, 5 A, 7.5 A, 10 A, 15 A, 20 A and 25 A
is 30% of their nominal rate.
Maximum load per circuit breaker rated 30 A is 20% of its nominal rate.