Load
Breaker Size
[A]
1A 4A 5A 7.5A 10A 15A 20A 25A 30A
Wire Size
[mm
2
/AWG]
1/18 1/18 1/18 1/18 1/18 2.5/14 2.5/14 4/12 4/12
Table 4-2 Cable Sizes
4.5.5 Battery Connections
WARNING Improper handling with batteries can be dangerous. Please read and understand
the information in the Safety chapter before connecting batteries.
CAUTION Follow closely the battery manufacturer’s specications regarding the
maximum battery charge current value. If the value is less than 5 A, Low Power Shelf
version is required.
WARNING The battery cables should be connected to the shelf as rst, then to the
batteries. If the battery cables are already connected to the batteries disconnect the -48 V
cable from the battery at least.
Battery connections are available at the rear of the system adjacent to the load connections,
see Figure 4-6.
To connect:
1. Remove sucient insulation from the
cable (max. 12mm). Make sure no single
stranded wire comes loose and touch any
other conductive wire.
2. Insert a at screwdriver into the square
opening of the battery connection to
release a spring latch.
3. Insert the stripped cable into the
appropriate round opening.
4. Connect the other end of the battery
cables to the batteries.