Page 16
BLUESTREAK SERIES
INSTALLATION & OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: BLUESTREAK-MAN Rev. 6
bluestreak-man-rev6-0719.indd
SIGNAL PIN CONNECTIONS
PIN FUNCTION PIN FUNCTION
A1
#MODULE PRESENT
C1
Sense +Ve
4
A2
GA6
C2 Current Monitor
4
A3
GA3
C3
GA1
A4
Standby Return
C4
5V Standby
1, 3
A5
#FANOK
C5
#DCOK
A6
#SMBALERT
C6
SCL
B1
Sense -Ve
D1
Remote Adjust
4
B2
Control
D2
Current Share
4
B3
GA2
D3
GA0
B4
Standby Return
D4
12V Standby
2, 3
B5
#TEMPOK
D5
#ACOK
B6
SDA
D6
#ENABLE
Notes:
1. Current rating of +5V standby is 1.8A.
2. Current rating of +12V standby is 0.8A.
3. Total standby consumption limited to 9.6W.
4. Referenced to -Ve Sense.
12.3 Mating Interface Board - Figure 7 shows a mating interface board which is available for
simplifying the testing of a BLUEstreak module. As shown in the photograph, provision
is made for input and output connections as well as the control and monitoring signals and
PMBus interface.
Figure 7 - Mating Interface Board