Page 17
BLUESTREAK SERIES
INSTALLATION & OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: BLUESTREAK-MAN Rev. 6
bluestreak-man-rev6-0719.indd
12.4 Output Voltage - The output voltage is factory set to its nominal value to an accuracy of
±1%. The voltage can be adjusted to any value within the range given in the table below
using the PMBus interface.
MODEL ADJUSTMENT
RANGE
TBSR3000, RBSR12/100
7.5-15V
TBSR5000, RBSR24/54, RBSR24/60
15-30V
TBSR7000, RBSR28/28, RBSR48/37
30-60V
12.5 Output Power & Current - The following table shows the maximum output power and
current ratings for the various models:
MAX.
POWER
OUTPUT
VOLTAGE
OUTPUT
CURRENT
INPUT
VOLTAGE
INPUT
CURRENT
MODEL
NO.
2000W
1500W
54.4VDC
37.0A
28.0A
180-264VAC
85-132VAC
10A
14A
RBSR48/37
1500W 54.4VDC 28.0A 85-264VAC 14A/7.5A RBSR48/28
2000W
1500W
48.0VDC
42.0A
31.0A
180-264VAC
85-132VAC
10A
14A
TBSR7000
1632W
1469W
27.2VDC
60.0A
54.0A
180-264VAC
85-132VAC
8.2A
13.5A
RBSR24/60
1469W 27.2VDC 54.0A 85-264VAC 13.5A/7.6A RBSR24/54
1440W 24.0VDC 60.0A 85-264VAC 13.3A/7.3A TBSR5000
1360W 13.6VDC 100.0A 85-264VAC 12.5A/7A RBSR12/100
1200W 12.0VDC 100.0A 85-264VAC 11.0A/6.5A TBSR3000
Models showing two output power levels with dual AC input ranges automatically limit the
output current according to the actual input voltage present.
When the output voltage is adjusted below the nominal voltage shown in the table the
maximum current indicated will apply. Conversely, when the output voltage is adjusted
above the nominal voltage shown the maximum power indicated will apply.
The maximum output power may be drawn up to +50°C air inlet temperature. Above +50°C
the total output power must be derated by 2.5%/°C, up to an absolute maximum air inlet
temperature of +70°C. Note that dependent on actual airow through the unit output power
may be further limited or a temperature alarm indicated at lower temperatures.
The two standby outputs of +5V @ 1.8A and +12V @ 0.8A are limited to a combined output
power of 9.6W.