Page 23
BLUESTREAK SERIES
INSTALLATION & OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: BLUESTREAK-MAN Rev. 6
bluestreak-man-rev6-0719.indd
SIGNAL CONNECTOR - J3
PIN FUNCTION PIN FUNCTION
1
Sense +Ve
4
Sense +Ve
J3 - Spring Clamp
6
1
2
Sense -Ve
5
Sense -Ve
3
Current Share
6
Current Share
SW1 provides a facility to alter the PMBus address of the power shelf in two ranges of 16
addresses: 0x20 to 0x3E and 0xA0 to 0xBE. The follow table denes the switch settings.
S1-1
GA6
S1-2
GA3
S1-3
GA2
MODULE ADDRESS
1 2 3 4
OFF OFF OFF 0xB8 0xBA 0xBC 0xBE
SW1
31
ON
OFF
OFF OFF ON 0xB0 0xB2 0xB4 0xB6
OFF ON OFF 0xA8 0xAA 0xAC 0xAE
OFF ON ON 0xA0 0xA2 0xA4 0xA6
ON OFF OFF 0x38 0x3A 0x3C 0x3E
ON OFF ON 0x30 0x32 0x34 0x36
ON ON OFF 0x28 0x2A 0x2C 0x2E
ON ON ON 0x20 0x22 0x24 0x26
Note: Module numbers 1 to 4 are left to right when viewed from the front (fan grille) end.
15.3 Dual Bus Power Shelves - Rear views of the dual bus types are shown in gure 10 below.
J1B J2B J1A J2A
AC4 AC3
+V +V -V-V Frame
Ground
AC2 AC1
OUTPUT A
200A Max. 200A Max.
OUTPUT B
0.625 (15.88) 1/4-20
8-32
0.5” length
Figure 10a - Model TBSR1UC with IEC Connectors
J1B J2B J1A J2A
AC4/AC3
or
DC4/DC3
+V +V -V-V Frame
Ground
AC2/AC1
or
DC2/DC1
0.437 (11.10)
OUTPUT A
200A Max. 200A Max.
OUTPUT B
0.625 (15.88) 1/4-208-32
8-32
0.5” length
Figure 10b - Model TBSR1U4D with Terminal Block Connections
AC inputs are supplied separately to each module either via IEC60320-C20 connectors or
terminal block connections. The terminal block connections are #8-32 threaded screws with
a 0.437” spacing, see gure 9b above.