Page 28
BLUESTREAK SERIES
INSTALLATION & OPERATING MANUAL
POWERING TECHNOLOGY
Document Number: BLUESTREAK-MAN Rev. 6
bluestreak-man-rev6-0719.indd
J1 J2 J3
SW1
OUTPUT A
AC4/AC3
or
DC4/DC3
+V +V -V-V
200A Max. 200A Max.
Frame
Ground
AC2/AC1
or
DC2/DC1
OUTPUT B
0.437 (11.10)
0.625 (15.88)
1/4-208-32
8-32
0.5” length
Figure 13 - DC Bus Bar Terminal Detail
17.5.1 Connecting Multiple Shelves in Parallel - Up to four power shelves can be
connected together to create higher capacity power systems than can be achieved
with a single shelf. UNIPOWER oers bus bar linking kits as follows:
2 shelf kit, part number 775-1509-0020. Contains two short link bars, one
for connecting the two positive bus bars together and one for connecting
the two negative bus bars together. The two link bars are identical and
interchangeable.
+V -V
+V -V
+V -V
3 shelf kit, part number 775-1509-0030. Contains two long link bars, one
for connecting the three positive bus bars together and one for connecting
the three negative bus bars together. The two link bars are identical and
interchangeable.
+V -V
+V -V
+V -V
4 shelf kit, part number 775-1509-0040. Contains two short link bars and
two long link bars. One short link bar and one long link bar are required for
connecting the four positive bus bars together and similarly for connecting
the four negative bus bars together. In each case the long bar is used to
connect the bus bars from three of the shelves and the short link bar is used
to connect the fourth shelf.
1/4-20 threaded bolts