UP-2210R/P Hardware installation and configuration manual
84
1.4 Configure using the PQ Online settings wizard
We recommend to select new setting to ensure good default values.
Select connection method corresponding with 1.3.1 above
Enter PT and CT ratio
Select measuring standard EN50160
1.4.1
Check main settings in Measure Configuration Summary. If you want to
change something go to
advanced
.
1.4.2 Enter a setting Name
1.4.3 You can save this configuration to a file for future use
1.4.4 Finish the wizard and update the meter active settings
Channel U4
1.4.13 Is U4 used? YES _____ NO ____ If NO, skip to 2.0.
1.4.14
Go to advanced->Disturbances->Voltage trig. Select suitable U4 sag/swell
trig. Recommended trig/Uref=10%
If ground fault monitoring select ca 10% of nominal voltage.
Note! Value is stated in
Volts
.
Channel I4
1.4.16 Is I4 used? YES ________ NO ________ . If no skip next step.
Go to advanced->Disturbances->Current trig. Select suitable I4 trig level.
Note! Value is stated in
Amps
.